Permit Information
Permit NumberFIR02-00185
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 3548 S FINDLEY AVE
Project NameSPR PETCO-FAMILY CENTER P-2
Customer Number 
ePlanReview 
Description
*PETCO-FAMILY CENTER PAD P2* To install a complete fire sprinkler system in a new 11,791 ft/2 retail tenant for pet grooming and protect the remaining 6,859 ft/2 (total vacant shell building, permitted under BLD01-03228. This building is constructed of concrete foundation and slab floors, masonry exterior walls, steel joist and metal roof with some wood framed overbuild. This building is fully fire sprinklered for area increase. This building and the building to the south were reviewed as all one building for allowable area provisions under the shell and core permit. It was noted in the Shell and Core permit that some Racking/Shelving exceeding 8' in height will be provided in the space. This fire permit is attached to the T.I. permit: BLD02-03229.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled7/26/20027/26/20027/26/2002PPASS
DetailsRick Jackson
Finaled by inspector at 7/26/2002 12:22:22 PM
INSP-Final Inspection7/26/20027/26/20027/26/2002PPASS
DetailsRick Jackson
INSP-Sprinkler Rough-in/Hydro7/2/20027/2/20027/2/2002PPART
DetailsRick Jackson
Scheduled by Inspector: 409 On 7/2/2002 12:44:50 PM hydro completed; need bell; tape off heads; anti freeze solution; test alarms 7/2/2002 2:27:54 PM
Sprinkler Plan Check5/14/2002 5/15/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/15/2002 DONE
DetailsBill Alexander
Plan assigned to (Bill)5/1/2002 5/15/2002 DONE
5/15/2002 08:02:19 JWA - activity updated through activity FIRA22 from case FIR02-00185.
Telephone call  5/15/2002 DONE
left mess that permit is ready
Issue permit  5/15/2002 DONE
Sprinkler Plan Check5/1/2002 5/14/2002 FAIL
DetailsBill Alexander
Lack correct maximum coverage (exceed 130 ft/2). RP backflow input was 2.5 lbs short in calculations. Remote test was not verified for 130 for friction loss spacing. Appears to have many obstructions with HVAC units which need clarified. Exterior control appear to not be impossible to install with this facility.
Application received  5/1/2002  
Case Summary    DONE
Inspection Record Card- Fire5/15/2002