Permit Information
Permit NumberFIR02-00186
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1733 S COLE RD
Project NameSPR CRACKER BARREL UPGRADE
Customer Number 
ePlanReview 
Description
(CRACKER BARREL OLD COUNTRY STORE, INC.) * TO UPGRADE FIRE SPRINKLER PROTECTION IN A 9,598 FT/2, SINGLE STORY TYPE V-N, FULLY FIRE SPRINKLERED RESTAURANT WITH GIFT SHOP. REMOVE EXISTING DRY SIDEWALLS IN OUTSIDE CANOPY. INSTALL A NEW ANTIFREEZE LOOP IN OUTSIDE CANOPY. INSTALL A BASE OF RISER FLEX CONNECTION. FIRE SPRINKLERS USED FOR AREA INCREASE. THE FIRE SPRINKLER SYSTEM WORK SHALL COMPLY WITH NFPA 13-1999, ATTACHED REVIEW COMMENT AND CONDITIONS LIST; AS REGULATED BY THE FIRE CHIEF. PERMIT AND FIRE "INSPECTION CARD" IS REQUIRED ON SITE AS A CONDITION FOR THIS WORK, TO PROVIDE WITNESS FOR COMPLIANCE VERIFICATION OF MINIMUM FIRE CODE. THIS PERMIT IS NOT ATTACHED TO A BUILDING PERMIT.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20029/19/20029/19/2002PPASS
DetailsTroy Cobbley
fire sprinkler system finaled
DOC - Permit Finaled9/19/20029/19/20029/19/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 9/19/2002 2:41:41 PM
INSP-Sprinkler Rough-in/Hydro6/28/20026/28/20026/28/2002PPASS
DetailsTroy Cobbley
Hydro test ok. Roughin is OK. Need to connect tamper switches to alarm panel, put spare heads in cabinet, provide signs and antifreeze 6/28/2002 3:12:22 PM
Inspection Record Card- Fire5/9/2002 5/9/2002 DONE
Telephone call  5/9/2002 DONE
CALLED BRODIE LEFT MESSAGE 5-9-02///DLD
Issue and Print Permit  5/9/2002 DONE
Plan assigned to (Bill)5/1/2002 5/9/2002 DONE
5/9/2002 08:30:12 JWA - activity updated through activity FIRA22 from case FIR02-00186.
Sprinkler Plan Check5/8/2002 5/9/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/9/2002 DONE
DetailsBill Alexander
Sprinkler Plan Check5/1/2002 5/7/2002 FAIL
Calculation method used was 7-2.3.4.2. Should have used 7-2.3.4.3.
Telephone call  5/7/2002 DONE
Called Brodie Stenquest (TVP) on concern with design. He is resubmitting calculations from 5 head test to 7.
Application received  5/1/2002  
Case Summary    DONE