INSP-Final Inspection | 9/19/2002 | 9/19/2002 | 9/19/2002 | P | PASS |
Troy Cobbley
|
|
|
fire sprinkler system finaled
|
DOC - Permit Finaled | 9/19/2002 | 9/19/2002 | 9/19/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 9/19/2002 2:41:41 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/28/2002 | 6/28/2002 | 6/28/2002 | P | PASS |
Troy Cobbley
|
|
|
Hydro test ok. Roughin is OK. Need to connect tamper switches to alarm panel, put spare heads in cabinet, provide signs and antifreeze 6/28/2002 3:12:22 PM
|
Inspection Record Card- Fire | 5/9/2002 | | 5/9/2002 | | DONE |
|
|
|
|
Telephone call | | | 5/9/2002 | | DONE |
|
|
|
CALLED BRODIE LEFT MESSAGE 5-9-02///DLD
|
Issue and Print Permit | | | 5/9/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/1/2002 | | 5/9/2002 | | DONE |
|
|
|
5/9/2002 08:30:12 JWA - activity updated through activity FIRA22 from case FIR02-00186.
|
Sprinkler Plan Check | 5/8/2002 | | 5/9/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/9/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 5/1/2002 | | 5/7/2002 | | FAIL |
|
|
|
Calculation method used was 7-2.3.4.2. Should have used 7-2.3.4.3.
|
Telephone call | | | 5/7/2002 | | DONE |
|
|
|
Called Brodie Stenquest (TVP) on concern with design. He is resubmitting calculations from 5 head test to 7.
|
Application received | | | 5/1/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|