INSP-Final Inspection | 5/8/2003 | 5/8/2003 | 5/8/2003 | P | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 5/8/2003 | 5/8/2003 | 5/8/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/8/2003 12:17:36 PM
|
INSP-Final Inspection | 7/29/2002 | 8/1/2002 | 8/1/2002 | A | FAIL |
Troy Cobbley
|
|
|
all items are ok except for fire alarm contractor needs to submitt fire alarm plans 8/1/2002 11:40:52 AM
|
INSP-Final Inspection | 7/9/2002 | 7/10/2002 | 7/10/2002 | A | FAIL |
Troy Cobbley
|
|
|
there is still encapsulated items throughout the stockrooms, heads still need the 6" clearance, tamper switch needs to be tested 7/10/2002 2:36:24 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/26/2002 | 6/27/2002 | 6/27/2002 | A | PASS |
Troy Cobbley
|
|
|
Hydro test for the in rack sprinkler system OK 6/27/2002 1:44:14 PM
|
INSP-Sprinkler Rough-in | 6/25/2002 | 6/26/2002 | 6/26/2002 | A | FAIL |
Troy Cobbley
|
|
|
mattresses must be stored below 12', product cannot be encapsulated, replace solid shelving with open shelving, maintain flu space behind the racking, maintain 6" min. clearance between sprinkler head and the top of the product, provide EQ at top of the 4" drop downs to the rack sprinklers or provide verification of non requirement, move EQ attachments to the top of the truss instead of the bottom or provide verification per NFPA 13. 6/26/2002 10:41:13 AM
|
Issue permit | | | 6/25/2002 | | DONE |
|
|
|
|
Telephone call | | | 5/24/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 5/20/2002 | | 5/23/2002 | | DONE |
|
|
|
5/23/2002 15:29:49 JWA - activity updated through activity FIRA22 from case FIR02-00202.
|
Sprinkler Plan Check | 5/20/2002 | | 5/23/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/23/2002 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 5/20/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/24/2002 | | | | |
|
|
|
|