INSP-Final Inspection | 8/21/2002 | 8/22/2002 | 8/22/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled 8/22/2002 1:00:31 PM
|
DOC - Permit Finaled | 8/22/2002 | 8/22/2002 | 8/22/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/22/2002 1:00:37 PM
|
INSP-Final Inspection | 8/21/2002 | 8/21/2002 | 8/21/2002 | A | FAIL |
Troy Cobbley
|
|
|
after flow of water the alarms rang in 40 seconds but the exterior alarm bell did not operate and needs replaced.
|
INSP-Final Inspection | 8/15/2002 | 8/16/2002 | 8/16/2002 | P | FAIL |
Troy Cobbley
|
|
|
flow of water did not activate the inside horn or the outside alarm bell, still need to test the 4" butterfly vavle 8/16/2002 2:39:52 PM
|
INSP-Final Inspection | 7/5/2002 | 7/9/2002 | 7/9/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide label in the fire alarm panel for the main breaker location, provide verification that the smoke detector is compatible with the fire alarm panel (its different from the cut sheets), block off spare outlet on the dedicated circuit, install correct orfice in the inspectors test outlet, test flow switch and 4" overhead valve, provide "knox box" 7/9/2002 2:35:28 PM
|
Issue permit | | | 6/7/2002 | | |
|
|
|
|
Plan assigned to (SAM) | 5/24/2002 | | 6/4/2002 | | DONE |
|
|
|
6/4/2002 13:57:37 430 - activity updated through activity FIRA22 from case FIR02-00211.
|
Alarm Plan Check | 6/4/2002 | | 6/4/2002 | | PASS |
Sam Rogers
|
|
|
Plans approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/4/2002 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 6/4/2002 | | 6/4/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/4/2002 | | DONE |
|
|
|
PERMIT READY
|
Alarm Plan Check | 5/30/2002 | | 5/30/2002 | | FAIL |
Sam Rogers
|
|
|
Plans denied. Review was only partial. Comments faxed to ADT.
|
Application received | | | 5/24/2002 | | |
|
|
|
|