DOC - Permit Finaled | 3/19/2003 | 3/19/2003 | 3/19/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/19/2003 2:28:14 PM
|
INSP-Final Inspection | 3/18/2003 | 3/18/2003 | 3/18/2003 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 3/19/2003 2:27:55 PM
|
INSP-Final Inspection | 2/4/2003 | 2/5/2003 | 2/5/2003 | A | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors are still installed incorrectly. No inspection done 2/5/2003 9:43:51 AM
|
INSP-Final Inspection | 1/2/2003 | 1/6/2003 | 1/6/2003 | A | CANC |
Troy Cobbley
|
|
|
The bank personel were not on site to give the contractor and I access. Inspection to be rescheduled 1/6/2003 10:26:02 AM
|
INSP-Final Inspection | 1/2/2003 | 1/7/2003 | 1/2/2003 | A | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 01/02/2003 at 14:34:31. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 01/02/2003 at 15:59:19.
|
INSP-Final Inspection | 1/2/2003 | 1/3/2003 | 1/2/2003 | A | CANC |
Troy Cobbley
|
|
|
###-#### Disp set to [CANC] by a contractor via Hello! on 01/02/2003 at 14:31:32.
|
INSP-Alarm Testing | 8/27/2002 | 8/28/2002 | 8/28/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide knox key box, provide proper orfice in the sprinkler system test line, move duct smoke detectors from the return side to the supply side, move smoke detector that is over the panel to the deck 8/28/2002 9:33:30 AM
|
INSP-Alarm Testing | 8/23/2002 | 8/27/2002 | 8/27/2002 | A | CANC |
Troy Cobbley
|
|
|
cancelled by contractor 8/27/2002 9:55:02 AM
|
Telephone call | | | 6/3/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 6/3/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 5/29/2002 | | 6/3/2002 | | DONE |
|
|
|
6/3/2002 09:16:21 430 - activity updated through activity FIRA22 from case FIR02-00214.
|
Alarm Plan Check | 6/3/2002 | | 6/3/2002 | | PASS |
Sam Rogers
|
|
|
Plans approved as noted.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/3/2002 | | DONE |
Sam Rogers
|
|
|
|
Application received | | | 5/29/2002 | | |
|
|
|
|
Inspection Record Card- Fire | 6/3/2002 | | | | |
|
|
|
|