INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 6/21/2002 9:21:12 AM inspection conducted at 1:30 - 2:30 am; additional inspection fee info provided to Linda H. In-duct detector not working for damper; requires reinspection 6/21/2002 9:23:31 AM
|
INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/21/2002 4:13:11 PM
|
DOC - Permit Finaled | 6/21/2002 | 6/21/2002 | 6/21/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/21/2002 4:13:40 PM
|
Plan assigned to (SAM) | 6/12/2002 | | 6/19/2002 | | DONE |
|
|
|
6/19/2002 10:20:02 SLR - activity updated through activity FIRA22 from case FIR02-00240.
|
Alarm Plan Check | 6/18/2002 | | 6/19/2002 | | PASS |
|
|
|
Resubmittal approved. Temporary installation of additional fire alarm devices in TI area connected to existing fire alarm system, which is to be replaced in near future. Plans approved subject to plan notes and field inspection; no written reveiw comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/19/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/19/2002 | | 6/19/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/19/2002 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 6/19/2002 | | |
|
|
|
|
Issue permit | | | 6/19/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/14/2002 | | HOLD |
|
|
|
Plan information inadequate for review. Additional information required; called Simplex; Stephanie cannont acces their file, she will call back on Monday 6/17 to discuss. Area of TI not idicated, occupancy of areas without a/v not indicated, purpose of 2 SD's not indicated, a/v appears improperly spaced, exits not identified, no SD shown above FACP-existing?
$:45 pm, called Tom Coglin, Layton Const., got most of necessary information by phone; will complete review on Moday.
|
Application received | | | 6/12/2002 | | |
|
|
|
|