INSP-Final Inspection | 10/29/2002 | 10/29/2002 | 10/29/2002 | A | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 10/29/2002 | 10/29/2002 | 10/29/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/29/2002 8:46:39 AM
|
INSP-Final Inspection | 9/20/2002 | 9/23/2002 | 9/23/2002 | A | PART |
Troy Cobbley
|
|
|
temporary occupancy was given for the sprinkler system, with dave millers permission. Several sprinkler heads are spaced too close. When the owner occupies the storage cabinets will be built to the ceiling to separate sprinklers 9/23/2002 10:05:39 AM
|
INSP-Final Inspection | 9/10/2002 | 9/11/2002 | 9/11/2002 | A | FAIL |
Troy Cobbley
|
|
|
fire sprinkler piping is ok for cover but I could not final due to no ceiling tile being installed 9/11/2002 8:17:08 AM
|
INSP-Final Inspection | 8/29/2002 | 8/30/2002 | 8/30/2002 | A | FAIL |
Troy Cobbley
|
|
|
"work room" will be used as storage and therefore will be considered ordinary hazard occupancy which means the sprinkler pendants are overspaced. 130sq ft max. Also the shelves only allow 16" of clearance instead of the 18" required. The sprinklers will need to be space to the shelves 8/30/2002 2:34:31 PM
|
Issue and Print Permit | | | 6/25/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/24/2002 | | 6/24/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/24/2002 | | DONE |
|
|
|
PERMIT READY AND FEES DUE
|
Plan assigned to (Bill) | 6/17/2002 | | 6/24/2002 | | DONE |
|
|
|
6/24/2002 14:35:54 JWA - activity updated through activity FIRA22 from case FIR02-00244.
|
Sprinkler Plan Check | 6/17/2002 | | 6/24/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/24/2002 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 6/17/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|