Permit NumberFIR02-00247
StatusFinaled
Name MOUNTAIN ALARM
Site Address 1750 W FRONT ST
Project NameALM-Grove Park Place
Customer Number 
ePlanReview 
Description
Grove Park Place - 7/29/2002 - Per resubmitted application, the scope is to replace the existing fire alarm panel with a new panel having the additional zones required to add monitoring of a new dry pipe sprinkler system, in addition to the existing wet sprinkler system monitoring which is currently provided.
The associated Fire Sprinkler permit FIR02-00133 is to install a Light Hazard added Dry Pipe System under an outside covered entry/canopy on an existing two story office building. Existing structure is sprinklered for one-hour substitution. The fire sprinkler system shall comply with NFPA 13-1999, red-lined plans, attached review comment and conditions list; as regulated by the Fire Chief. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  7/25/2007  
Case Summary  7/22/2004  
INSP-Final Inspection11/6/200211/8/200211/8/2002APASS
DetailsRick Jackson
robert; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
DOC - Permit Finaled11/8/200211/8/200211/8/2002PPASS
DetailsRick Jackson
Finaled by inspector at 11/8/2002 12:57:30 PM
INSP-Final Inspection10/28/200210/31/200210/31/2002AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/28/2002 at 12:05:02. Contact: . need tampered ball valve switch on new dry system riser; lockpouts for air compressor and FACP breakers; need to complete testing of the new dry system air and flow switches 10/31/2002 10:45:14 AM
INSP-Alarm Testing10/21/200210/22/200210/22/2002ANR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/21/2002 at 12:08:05. Contact: ###-####. will reschedule for next week 10/22/2002 4:14:49 PM
Issue permit  8/28/2002 DONE
Alarm Plan Check  8/15/2002 PASS
Acceptable per resubmittal received 8/8/02; Address changed from 501 E. Baybrook Crt to 1750 W. Front St.
PLANS/APPL TAKEN TO FRONT DESK  8/15/2002 DONE
Plan assigned to (SAM)6/18/2002 8/15/2002 DONE
8/15/2002 17:18:29 SLR - activity updated through activity FIRA22 from case FIR02-00247.
Alarm Plan Check7/19/2002 7/30/2002 FAIL
Address shown does not match the AS permit issued for the dry pipe va modification. Also design issues need to be addressed. Attempted to resolve by phone with Mountain Alarm 7/29 amd 7/30 but could not get answers from Bob Colter. Faxed revised review coments to Mountain Alarm for review by Robert Bailey.
Alarm Plan Check  6/28/2002 FAIL
Application and plans incomplete; inadequate for review. Requirements for additional information faxed to Mountain Alarm.
Application received  6/18/2002