Permit NumberFIR02-00250
StatusFinaled
Name GENERAL FIRE INC
Site Address 1000 E PARK BLVD
Project Namealm-ST LUKES
Customer Number 
ePlanReview 
Description
ST LUKES - To install a new alarm system within an existing, 42,000 sq ft, sprinklered, building. The alarm system will include monitoring of the fire sprinkler system and duct smoke detectors for HVAC air handler shut-down, and off-site alarm monitoring.
The associated building permit (BLD 02-01218) is to: Within the existing 42,000 sq. ft building, add a new overhead door and new exit access door with landings within a 26,400 sq. ft. warehouse storage area. Work includes cutting out an 10'-8" high by 11'-4" wide portion of the existing masonry wall to allow installation of a new overhead door per engineering and plans. NOTE: Existing bond beam over new opening to remain in place. Existing roof truss system runs parallel to the new opening. To install bracing at top of existing CMU wall per plan. To upgrade exit system by installing appropriate landing on both sides of a minimum 3'-0" x 6'-8" man door to be located in the NW corner of the storage warehouse, a location of a previous exit door. To add hand rails as required at all stairs & ramps; verify exit door hardware, exit signage & illumination; verify draft stops in attic and sprinkler & alarm system throughout building. NOTE: The sprinkler system is required for allowable area increase for code compliance of existing building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/12/200212/12/200212/12/2002PPASS
DetailsRick Jackson
DOC - Permit Finaled12/12/200212/12/200212/12/2002APASS
DetailsRick Jackson
Finaled by inspector at 12/12/2002 10:55:24 AM
Issue and Print Permit  11/1/2002 DONE
Telephone call  10/31/2002 DONE
left mess that permit is ready
Miscellaneous action  10/31/2002 DONE
took 100.00 from fir02-00343 and applied to this permit(fir02-00250) instead of refund
Alarm Plan Check10/31/2002 10/31/2002 PASS
DetailsSam Rogers
Resubmittal for field modifications using spot type smoke detectors instead of duct type smoke detectors which won't fit in the duct work. The propose design is not in strict accordance with the 1997 UMC section 608 exception #1 but does meet the 2000 IMC 606.2.1 exception.
PLANS/APPL TAKEN TO FRONT DESK  10/31/2002 DONE
DetailsSam Rogers
Plan assigned to (SAM)10/24/2002 10/24/2002 DONE
INSP-Alarm Testing10/17/200210/18/200210/18/2002AFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need door/FACP keys for knox box; resubmittal needed for changes to detectors on east side of building that are used for AHU shutdown (plans show duct detectors but due to location of duct work duct detectors couldn't be installed - using smoke detectors on ceiling instead as walls go to the deck and this unit serves onlt the two rooms; UMC 608 exception 1); duct detector by lobby not shutting unit off 10/18/2002 10:27:24 AM
INSP-Conference8/8/20028/8/20028/8/2002PPART
DetailsRick Jackson
###-#### met with Quality Electric about installation of duct detectors on the east unit; wanted to use the exception and install spot detectors in the rooms served by this unit; will have to resubmit through PDS plan review 8/8/2002 1:37:50 PM
Inspection Record Card- Fire7/12/2002 7/12/2002 DONE
Telephone call  7/12/2002 DONE
permit ready and fees due
Issue permit  7/12/2002 DONE
Plan assigned to (SAM)6/20/2002 7/11/2002 DONE
7/11/2002 17:37:00 SLR - activity updated through activity FIRA22 from case FIR02-00250.
Alarm Plan Check  7/11/2002 PASS
resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  7/11/2002 DONE
Alarm Plan Check  6/28/2002 FAIL
review comments faxed to General Fire.
Application received  6/20/2002  
Inspection Record Card- Fire10/31/2002