INSP-Final Inspection | 12/12/2002 | 12/12/2002 | 12/12/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 12/12/2002 | 12/12/2002 | 12/12/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/12/2002 10:55:24 AM
|
Issue and Print Permit | | | 11/1/2002 | | DONE |
|
|
|
|
Telephone call | | | 10/31/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Miscellaneous action | | | 10/31/2002 | | DONE |
|
|
|
took 100.00 from fir02-00343 and applied to this permit(fir02-00250) instead of refund
|
Alarm Plan Check | 10/31/2002 | | 10/31/2002 | | PASS |
Sam Rogers
|
|
|
Resubmittal for field modifications using spot type smoke detectors instead of duct type smoke detectors which won't fit in the duct work. The propose design is not in strict accordance with the 1997 UMC section 608 exception #1 but does meet the 2000 IMC 606.2.1 exception.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/31/2002 | | DONE |
Sam Rogers
|
|
|
|
Plan assigned to (SAM) | 10/24/2002 | | 10/24/2002 | | DONE |
|
|
|
|
INSP-Alarm Testing | 10/17/2002 | 10/18/2002 | 10/18/2002 | A | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need door/FACP keys for knox box; resubmittal needed for changes to detectors on east side of building that are used for AHU shutdown (plans show duct detectors but due to location of duct work duct detectors couldn't be installed - using smoke detectors on ceiling instead as walls go to the deck and this unit serves onlt the two rooms; UMC 608 exception 1); duct detector by lobby not shutting unit off 10/18/2002 10:27:24 AM
|
INSP-Conference | 8/8/2002 | 8/8/2002 | 8/8/2002 | P | PART |
Rick Jackson
|
|
|
###-#### met with Quality Electric about installation of duct detectors on the east unit; wanted to use the exception and install spot detectors in the rooms served by this unit; will have to resubmit through PDS plan review 8/8/2002 1:37:50 PM
|
Inspection Record Card- Fire | 7/12/2002 | | 7/12/2002 | | DONE |
|
|
|
|
Telephone call | | | 7/12/2002 | | DONE |
|
|
|
permit ready and fees due
|
Issue permit | | | 7/12/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 6/20/2002 | | 7/11/2002 | | DONE |
|
|
|
7/11/2002 17:37:00 SLR - activity updated through activity FIRA22 from case FIR02-00250.
|
Alarm Plan Check | | | 7/11/2002 | | PASS |
|
|
|
resubmittal acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/11/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/28/2002 | | FAIL |
|
|
|
review comments faxed to General Fire.
|
Application received | | | 6/20/2002 | | |
|
|
|
|
Inspection Record Card- Fire | 10/31/2002 | | | | |
|
|
|
|