Permit Information
Permit NumberFIR02-00253
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 7009 W FRANKLIN RD
Project Namealm-Bishop Kelly High School
Customer Number 
ePlanReview 
Description
Bishop Kelly High School - FIR02-00173 is to be VOIDED and replaced with this permit. These plans replace the alarm plans previously approved under FIR02-00173 (which have not yet been field inspected), due to extensive changes that were required at the field level to those approved plans.
Scope of this project is to replace the existing fire alarm panel with a new FAC panel and upgrade the entire building fire alarm system to meet current Code requirements. These revised plans add additional initiating devices, horn/strobes and speaker/strobes, a new NAC panel, and completely revise the alarm circuitry.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Agreement of Future work8/1/200210/1/20037/24/2003  
letter dated 7-29-02; School Principal agrees that by 10-1-03 they will either install smoke detectors in beam pockets or install ceiling with appropriate SD to complete this Permit. Work Completed per FIR03-00314.
INSP-Final Inspection1/14/20031/14/20031/14/2003PPASS
DetailsTroy Cobbley
Fire alarm system to be finaled per Sam Rogers since upgrade agreement has been made. To be completed october 1, 2003
DOC - Permit Finaled1/14/20031/14/20031/14/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 1/14/2003 12:53:05 PM
INSP-Final Inspection8/15/20028/16/20028/16/2002APART
DetailsTroy Cobbley
Fire alarm system given a temporary occupancy until the layin ceiling tile is installed which will eliminate the beam pockets and the requirement for smoke detectors in each one. This work will be done no later than Oct 1 2003 per letter agreed upon by Dave Miller with the Boise Fire Dept 8/16/2002 10:20:32 AM
INSP-Alarm Testing7/25/20027/26/20027/26/2002AFAIL
DetailsTroy Cobbley
signals to the monitoring station are incorrect, a/v's are overspaced in classrooms, smoke detectors overspaced due to beams in corridors and rooms. I stopped the inspection. Basically inspection needs to start at the beginning. 7/26/2002 10:35:22 AM
Plan assigned to (SAM)6/24/2002 7/2/2002 DONE
7/2/2002 10:58:26 SLR - activity updated through activity FIRA22 from case FIR02-00253.
Alarm Plan Check  7/2/2002 PASS
PLANS/APPL TAKEN TO FRONT DESK  7/2/2002 DONE
Inspection Record Card- Fire7/2/2002 7/2/2002 DONE
Issue and Print Permit  7/2/2002 DONE
Application received  6/24/2002