INSP-Final Inspection | 7/26/2002 | 7/26/2002 | 7/26/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 7/26/2002 | 7/26/2002 | 7/26/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 7/26/2002 3:45:18 PM
|
CHANGE STATUS TO (ISS) | | | 7/26/2002 | | DONE |
|
|
|
already pd
|
Plan assigned to (SAM) | 6/27/2002 | | 7/26/2002 | | DONE |
|
|
|
7/26/2002 11:17:01 SLR - activity updated through activity FIRA22 from case FIR02-00260.
|
Telephone call | | | 7/26/2002 | | DONE |
|
|
|
permit ready
|
Inspection Record Card- Fire | 7/26/2002 | | 7/26/2002 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/26/2002 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/25/2002 | | PASS |
|
|
|
|
Alarm Plan Check | 7/25/2002 | | 7/25/2002 | | PASS |
|
|
|
Resubmittal received of proposed alarm upgrade agreement to met curren high rise code requirements. Plans approved upon condition of future programmed upgrades as agreed to by the FD.
|
Alarm Plan Check | | | 7/3/2002 | | FAIL |
|
|
|
Plans do not meet high rise building alarm requirements. Discussed with Rick Groomes at Northwest; he was aware that the proposed design does not meet Code, but wanted it in writing. Review comments faxed to Northwest Sales.
|
Application received | | | 6/27/2002 | | |
|
|
|
|