INSP-Final Inspection | 8/2/2002 | 8/2/2002 | 8/2/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 8/2/2002 | 8/2/2002 | 8/2/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/2/2002 1:36:42 PM
|
INSP-Final Inspection | 7/30/2002 | 7/31/2002 | 7/31/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/30/2002 at 14:08:58. Contact: ###-####.
|
Telephone call | | | 7/31/2002 | | DONE |
|
|
|
2:15pm - Rick called to say lines sizes are diferent than shown on the plan. Was instructed to verify line sizes to match existing for number of heads on each size piping. Appears to be 2 heads on 1" and 3 heads on 1 1/4" for tree lines. Grid appeared to be all 1". Instructed Rick (his option) to require resubmittal from Grinnell to match actual piping.
|
Issue permit | | | 7/25/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/23/2002 | | 7/23/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/12/2002 | | 7/23/2002 | | DONE |
|
|
|
7/23/2002 10:33:28 JWA - activity updated through activity FIRA22 from case FIR02-00280.
|
Sprinkler Plan Check | 7/22/2002 | | 7/23/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/23/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 7/17/2002 | | DONE |
|
|
|
plans denied called to have plans picked up
|
Sprinkler Plan Check | 7/12/2002 | | 7/16/2002 | | FAIL |
Bill Alexander
|
|
|
Lack system design information (original) and possibly modifying protection beyond original system design (more than one head on one drop). Original pipe sizes not provided. Statement of head area spacing relates to NFPA 13's maximum with no proof system was actually designed for that.
|
Miscellaneous action | | | 7/16/2002 | | DONE |
|
|
|
Took denied set of plans to the the front desk for calling and return to designer.
|
Telephone call | | | 7/16/2002 | | DONE |
|
|
|
Faxed copy of denied review notes to Simplex Grinnell.
|
Application received | | | 7/12/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|