INSP-Final Inspection | 12/17/2002 | 12/20/2002 | 12/20/2002 | A | PASS |
Troy Cobbley
|
|
|
###-#### Brad
|
DOC - Permit Finaled | 12/20/2002 | 12/20/2002 | 12/20/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 12/20/2002 8:43:44 AM
|
Issue permit | | | 12/20/2002 | | |
|
|
|
|
INSP-Final Inspection | 11/7/2002 | 11/13/2002 | 11/13/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide tamper switch on gate valve on fire pump test line, verify weather proof pull station assembly, provide hi/low pressure switch for anechoic chamber dry pipe valve 11/14/2002 1:42:18 PM
|
Inspection Record Card- Fire | 7/25/2002 | | 7/25/2002 | | DONE |
|
|
|
|
Telephone call | | | 7/25/2002 | | DONE |
|
|
|
PERMIT READY AND FEES DUE
|
Plan assigned to (SAM) | 7/15/2002 | | 7/24/2002 | | DONE |
|
|
|
7/24/2002 17:11:22 SLR - activity updated through activity FIRA22 from case FIR02-00286.
|
Alarm Plan Check | 7/24/2002 | | 7/24/2002 | | PASS |
|
|
|
Additional information provided; adequate for review.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 7/15/2002 | | 7/22/2002 | | HOLD |
|
|
|
Insufficient description of scope of work. Hold for discussion with Simplex or HP.
|
Application received | | | 7/15/2002 | | |
|
|
|
|