DOC - Permit Finaled | 9/4/2002 | 9/4/2002 | 9/4/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/4/2002 8:31:34 AM
|
INSP-Final Inspection | 9/4/2002 | 9/4/2002 | 9/4/2002 | A | PASS |
Rick Jackson
|
|
|
tested dry system trip test and alarms/tampers - okay
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2002 | 8/29/2002 | 8/29/2002 | A | PART |
Rick Jackson
|
|
|
overhead hydro okay on system in gym under bleachers in shower/locker room only 8/29/2002 10:59:04 AM
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2002 | 8/28/2002 | 8/28/2002 | P | FAIL |
Rick Jackson
|
|
|
hydro on area in gym and under seats wouldn't hold pressure
|
INSP-Sprinkler Rough-in/Hydro | 8/22/2002 | 8/23/2002 | 8/23/2002 | P | PART |
Rick Jackson
|
|
|
air test 24 hour air test okay on dry system 8/23/2002 1:28:18 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/22/2002 | 8/23/2002 | 8/23/2002 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/22/2002 at 16:07:34. Contact: ###-####. hydro on all overhead okay; tested wet system alarms okay; need to test dry system alarms/tampers; dry uprights not installed 8/26/2002 8:37:42 AM
|
INSP-Sprinkler Rough-in/Hydro | 8/21/2002 | 8/22/2002 | 8/22/2002 | A | PART |
Rick Jackson
|
|
|
###-#### LONNY started 24 hr air test 8/22/2002 3:47:55 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/16/2002 | 8/19/2002 | 8/19/2002 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/16/2002 at 14:06:03. Contact: ###-####. okay to cover west existing areas; dry valve not complete; will need to reverify combustibles sheet rocked in corridors on both floors 8/19/2002 3:52:14 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/14/2002 | 8/15/2002 | 8/15/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/14/2002 at 11:34:00. Contact: ###-####. 4 inch main requires hangers per TJI instrcutions; need proper temp heads in west stair; complete EQ'ing; storage under heads in classrooms within 18 inches of head due to shelf; this covers only the west existing portion, new addition and gym not ready 8/15/2002 12:01:05 PM
|
Issue permit | | | 8/14/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/8/2002 | | 8/9/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/9/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 8/9/2002 | | DONE |
|
|
|
CALLED TO HAVE THEM PICK UP REVISED PLANS
|
Inspection Record Card- Fire | 8/5/2002 | | 8/5/2002 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/5/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/2/2002 | | 8/2/2002 | | DONE |
|
|
|
|
Telephone call | | | 8/2/2002 | | DONE |
|
|
|
permit ready and fees due
|
Plan assigned to (Bill) | 7/25/2002 | | 8/2/2002 | | DONE |
|
|
|
8/2/2002 07:37:08 JWA - activity updated through activity FIRA22 from case FIR02-00309.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/2/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 7/25/2002 | | 8/1/2002 | | PART |
Bill Alexander
|
|
|
Work may proceed. Plan resubmittal required prior to full acceptance.
|
Miscellaneous action | | | 7/29/2002 | | DONE |
|
|
|
TV requested this project be replaced with FIR02-00311 (Idaho Statesman), in sequence.
|
Application received | | | 7/25/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|