Permit Information
Permit NumberFIR02-00310
StatusFinaled
Name SIMPLEX/GRINNELL FIRE PROTECTION
Site Address 1404 W MAIN ST
Project NameSPR FIRST NATIONAL PAWN
Customer Number 
ePlanReview 
Description
(FIRST NATIONAL PAWN) To modify the riser and extend a fire sprinkler system into a remodeled 17,368 ft/2 one story building, (11,820 square foot main floor and 5,548 square foot basement). A 5,235 square foot retail sales room is being created on the main floor. The 5,548 square foot basement will retain its storage occupancy. Construction with appropriate fire protection includes interior nonbearing walls and suspended ceilings. The fire sprinkler system must be installed and operational prior to a Certificate of Occupancy being issued to this tenant. The basement of this building has and existing sprinkler system. This building requires full fire sprinklers throughout, to avoid the 1-hr occupancy separations at storage rooms. All fire sprinkler system work shall comply with NFPA 13?1999, attached review comment and conditions list; as regulated by the fire chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit BLD02-01818.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/30/200210/31/200210/31/2002APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/30/2002 at 15:10:53. Contact: ###-####.
DOC - Permit Finaled10/31/200210/31/200210/31/2002PPASS
DetailsRick Jackson
Finaled by inspector at 10/31/2002 6:41:59 PM
INSP-Final Inspection9/12/20029/13/20029/13/2002ACANC
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung not a final inspection see flush for this date 9/13/2002 1:40:39 PM
INSP-Supply line flush9/13/20029/13/20029/13/2002PPART
DetailsRick Jackson
flushed underground and hydro okay for underground; attempted to forward flow the backflow preventer - couldn't get the required gpm's with the equipment on hand
INSP-Sprinkler Rough-in9/12/20029/12/20029/12/2002PPART
DetailsRick Jackson
PIV installed and okay to cover
INSP-Sprinkler Rough-in/Hydro9/9/20029/10/20029/10/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 09/09/2002 at 08:01:00. Contact: ###-####. heads overspaced at corridor wall in showroom; add head at main entrance; PIV not installed; FDC will rewuire sign to prevent parking blocking it; add 911 on outside bell; test alarms when installed; hydro okay 9/10/2002 3:57:43 PM
Sprinkler Plan Check9/10/2002 9/10/2002 PASS
DetailsBill Alexander
Stamped corrected plans
Issue permit  9/6/2002 DONE
Sprinkler Plan Check9/4/2002 9/4/2002 PASS
DetailsBill Alexander
Modified underground PIV location. Returned acceptance with fax and letter.
Inspection Record Card- Fire8/29/2002 8/29/2002 DONE
Telephone call  8/29/2002 DONE
permit ready and fees due
Sprinkler Plan Check8/21/2002 8/28/2002 PART
DetailsBill Alexander
Required revised plan submittal meeting minimum code.
PLANS/APPL TAKEN TO FRONT DESK  8/28/2002 DONE
DetailsBill Alexander
Plan assigned to (Bill)7/26/2002 8/28/2002 DONE
8/28/2002 15:43:16 JWA - activity updated through activity FIRA22 from case FIR02-00310.
Sprinkler Plan Check7/26/2002 8/8/2002 FAIL
DetailsBill Alexander
Warehouse storage piping design for OH-1 Occupancy and should be OH-2. No outside control on systems. Heads overspaced and areas have "shadowing". Need to verify cavity with calcs. Need backflow forward flow test connection. Need dry system capacity. Need compressor data submittals. Need final calculation head analysis. Need to verify hydrant location and FDC access on the plans. Need more than a generic earthquake detail (engineering required). 155 degree heads in the cavities and etc.
Miscellaneous action  8/8/2002 DONE
Took plans to front desk for calling and returning. Faxed copy of review to Grinnell (2:45pm)
Telephone call  8/8/2002 DONE
CALLED TO HAVE DENIED PLANS PICKED UP
Application received  7/26/2002  
Case Summary    DONE