Permit Information
Permit NumberFIR02-00317
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 825 W FORT ST
Project Namealm-ST JOSEPH'S SCHOOL
Customer Number 
ePlanReview 
Description
ST JOSEPH'S SCHOOL - To add alarm devices within the new addition area and monitoring of the new fire sprinkler system installed throughout the entire school building, including the new addition, connected to the existing building fire alarm system. Alarm coverage within the new addition includes manual pull stations, selective coverage smoke detection for release of fire door hold-opens and elevator recall, supplementary coverage smoke detection in classrooms, fire sprinkler system monitoring, in-duct smoke detectors for release of fire/smoke dampers, and horn/strobe devices.
The associated building permit (BLD 02-00505) is to construct a two-story, Type V 1hr classroom addition between the existing classrooms and gym. Includes (5) classrooms, media ctr. expansion, storage room, new ramp, and a elevator. Materials will match the existing building w/brick and stucco and windows, wd trim will match adjacent finishes. Entire building will receive a new fire sprinklers system throughout which will be used for substitution of one-hour construction. Fire Sprinkler and Fire Alarm require separate permitting and approval, as regulated by the Fire Chief. All work is per approved plans and attachments RH01-00243. Area of the addition is 3, 429.5 square feet for the 1st and 2nd floors with a total of 6,859 sq. ft.
The associated fire sprinkler permit FIR02-00309 is to install a new fire sprinkler system in a 22,077 ft/2 school which includes a 6,859 ft/2 (3,430 ft/2 1st floor, 3,429 2nd floor) two story, Type V 1hr classroom addition, between the existing classrooms and gymnasium. The new addition work includes five classroom, a media center expansion, a storeroom, new ramp, and a new elevator. Fire sprinklers system will be used for substitution of one-hour construction. Underground fire service supply was permitted under FIR02-00265. This permit is attached to building permit: BLD02-00505.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/4/20029/4/20029/4/2002APASS
DetailsRick Jackson
DOC - Permit Finaled9/4/20029/4/20029/4/2002APASS
DetailsRick Jackson
Finaled by inspector at 9/4/2002 8:32:42 AM
INSP-Alarm Testing8/23/20028/23/20028/23/2002PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 08/23/2002 at 08:00:25. Contact: ###-####. tested alarms; need to test the dry system alarms/tampers as it is now wet; detector at damper in 1 hour wall for damper release not working - damper will be kept closed until it can be repaired; elevator recall/shunt not tested as the elevator is not certified by state; alarms in new addition tested okay 8/26/2002 8:36:46 AM
Inspection Record Card- Fire8/21/2002 8/21/2002 DONE
Telephone call  8/21/2002 DONE
Issue permit  8/21/2002 DONE
Meeting  8/20/2002 DONE
meeting held with Simplex representatives Peter Petroni and Chris, and Marv Merkel, Eidam Assoc., system designer, to clarify plans.
Alarm Plan Check  8/20/2002 PASS
Arppoved with CONDITIONS
PLANS/APPL TAKEN TO FRONT DESK  8/20/2002 DONE
Alarm Plan Check8/9/2002 8/19/2002 FAIL
Resubmittal received 8/9. Zoning of fire smoke damper detectors has been corrected but but the 1-line clouding of changes does not match the plan clouding and no explanation is given on application of scope of work. Previous application received 8/6 indicated scope of work was for a TI project, however, the associated buidling permit is for a new 6,859 sq. ft, 2-story addition and to install a new fire sprinkler system througout the entire 22,000 sq.ft school. A sprinkler permit for this work was issued 8/9/02, but the alarm plans do not show the entire building, so it cannot be determined if the alarm plans include the new sprinkler system design. New/existing devices still not distiquished on plans. Called Eidam; John Vandergraf will have the system designer call me tomorrow. Hold to discuss further with Simplex and Eidam.
Plan assigned to (SAM)8/6/2002 8/9/2002 DONE
8/9/2002 13:47:56 JWA - activity updated through activity FIRA22 from case FIR02-00309.
Alarm Plan Check8/6/2002 8/7/2002 FAIL
Resubmittal received 8/6. F/S dmaper detectors couluded, quick glance indicates zoning is incorrect. Per telcon with Simplex, Stephanie Cribb, they knew it was but could not change design; HOLD review for next resubmittal; Eidam is redesigning the plans. No written review done.
Application received  8/6/2002  
Alarm Plan Check7/29/2002 8/2/2002 FAIL
No explanation on application of scope of work and no clouding or other identification on plans of modifications. Can't determine scope of the project. Therefore no plan review done. Discussed with Sean and Stephanie and plans returned to Simplex 8/2/02 for revision and resubmittal.