INSP-Final Inspection | 4/23/2003 | 4/24/2003 | 4/24/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/23/2003 at 2:18:51 PM. Contact: ###-####. tested in-duct detector; damper closed 4/24/2003 10:21:10 AM
|
DOC - Permit Finaled | 4/24/2003 | 4/24/2003 | 4/24/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 4/24/2003 10:21:14 AM
|
INSP-Final Inspection | 3/17/2003 | 3/18/2003 | 3/18/2003 | P | FAIL |
Troy Cobbley
|
|
|
In-duct detector did not work 3/18/2003 1:06:18 PM
|
INSP-Final Inspection | 1/30/2003 | 1/31/2003 | 1/31/2003 | P | NR |
Troy Cobbley
|
|
|
ADT was not ready for the inspection 1/31/2003 2:04:13 PM
|
INSP-Final Inspection | 1/21/2003 | 1/24/2003 | 1/24/2003 | P | FAIL |
Troy Cobbley
|
|
|
###-#### matt The south in-duct smoke detector did not operate and needs to be tested. Provide map at the FACP. Verify dedicated circuit location 1/24/2003 3:59:07 PM
|
INSP-Final Inspection | 10/11/2002 | 10/14/2002 | 10/14/2002 | P | CANC |
Troy Cobbley
|
|
|
duplicate inspection. The contractor said he punched in the wrong button and forgot to cancell 10/14/2002 4:27:08 PM
|
INSP-Final Inspection | 10/11/2002 | 10/14/2002 | 10/14/2002 | A | FAIL |
Troy Cobbley
|
|
|
verify dedicated electrical circuit to FACP has been completed, clean up wiring in the FACP, verify batteries in FACP are supervised after the panel gets cleaned up, duct smoke detectors do nto activate the fie smoke dampers as per the review comments, change labeling on the new tamper switch 10/14/2002 10:48:58 AM
|
INSP-Final Inspection | 10/8/2002 | 10/10/2002 | 10/10/2002 | P | CANC |
Troy Cobbley
|
|
|
contractor cancelled 10/10/2002 3:15:32 PM
|
Issue permit | | | 8/29/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 8/12/2002 | | 8/23/2002 | | DONE |
|
|
|
8/23/2002 15:14:29 430 - activity updated through activity FIRA22 from case FIR02-00325.
|
Alarm Plan Check | 8/23/2002 | | 8/23/2002 | | PASS |
Sam Rogers
|
|
|
Plans approved as noted
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/23/2002 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 8/23/2002 | | 8/23/2002 | | DONE |
|
|
|
|
Telephone call | | | 8/23/2002 | | DONE |
|
|
|
PERMIT READY AND FEES DUE
|
Application received | | | 8/12/2002 | | |
|
|
|
|