INSP-Final Inspection | 1/31/2003 | 1/31/2003 | 1/31/2003 | P | PASS |
Rick Jackson
|
|
|
###-####
|
DOC - Permit Finaled | 1/31/2003 | 1/31/2003 | 1/31/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/31/2003 1:49:17 PM
|
INSP-Final Inspection | 1/22/2003 | 1/24/2003 | 1/24/2003 | P | FAIL |
Rick Jackson
|
|
|
###-#### door releases still not working; strobe in wrestling room still not working; need updated map at panel; provide as builts to school 1/24/2003 3:38:49 PM
|
INSP-Final Inspection | 1/16/2003 | 1/17/2003 | 1/17/2003 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/16/2003 at 09:35:59. Contact: ###-####.
|
INSP-Final Inspection | 1/17/2003 | 1/17/2003 | 1/17/2003 | P | FAIL |
Rick Jackson
|
|
|
NAC circuits aren't wired per plans; circuits at panels are mixed up; strobe not working wrestling room and room 209; door holders not releasing on alarm; need resubmittals for NAC wiring; need to test tampers and flows for both systems and complete testing of cafeteria 1/17/2003 4:47:38 PM
|
FIR-Aging Inspection | 1/9/2003 | 1/9/2003 | 1/9/2003 | | NR |
Rick Jackson
|
|
|
talked to Alarmco and they will schedule for next week 1/9/2003 12:30:20 PM
|
Telephone call | | | 10/9/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 10/9/2002 | | |
|
|
|
|
Plan assigned to (SAM) | 8/14/2002 | | 10/8/2002 | | DONE |
|
|
|
10/8/2002 15:52:43 SLR - activity updated through activity FIRA22 from case FIR02-00331.
|
Alarm Plan Check | | | 10/8/2002 | | PASS |
|
|
|
Plans approved based on e-mail from architect, CSHQA, indicating the school's commitment to upgrade the cafeteria "building" FA devices under a separate alarm contract, before 12/31/2002.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/8/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/28/2002 | | FAIL |
|
|
|
CONDITIONAL APPROVAL given to begin field installation prior to approval of resubmittal and issuance of the FA permit. Review comments dicussed with and faxed to Alan @ Alarmco.
|
Application received | | | 8/14/2002 | | |
|
|
|
|
Inspection Record Card- Fire | 10/8/2002 | | | | |
|
|
|
|