Permit Information
Permit NumberFIR02-00331
StatusFinaled
Name ALARMCO
Site Address 1105 N 13TH ST
Project Namealm-IND SCHOOL DIST OF BOISE C
Customer Number 
ePlanReview 
Description
IND SCHOOL DIST OF BOISE CITY, North Jr. High - Adding manual pull stations, a sprinkler flow switch and four valve tampers on a new sprinkler system being installed in the basement of the main building, new a/v notification devices, and three new NAC panel power extender panels, to an existing fire alarm system.
This permit is not attached to any building permit; however, it is associated with a fire sprinkler permit (FIR02-00272) to provide sprinklers in the 11,700 sq ft basement of the main building.
NOTE: This permit is not for a full alarm system upgrade. Approval of this permit does not imply approval of existing devices, which are not modified under this permit; existing deficiencies may be required to be upgraded at a later date.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/31/20031/31/20031/31/2003PPASS
DetailsRick Jackson
###-####
DOC - Permit Finaled1/31/20031/31/20031/31/2003PPASS
DetailsRick Jackson
Finaled by inspector at 1/31/2003 1:49:17 PM
INSP-Final Inspection1/22/20031/24/20031/24/2003PFAIL
DetailsRick Jackson
###-#### door releases still not working; strobe in wrestling room still not working; need updated map at panel; provide as builts to school 1/24/2003 3:38:49 PM
INSP-Final Inspection1/16/20031/17/20031/17/2003ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 01/16/2003 at 09:35:59. Contact: ###-####.
INSP-Final Inspection1/17/20031/17/20031/17/2003PFAIL
DetailsRick Jackson
NAC circuits aren't wired per plans; circuits at panels are mixed up; strobe not working wrestling room and room 209; door holders not releasing on alarm; need resubmittals for NAC wiring; need to test tampers and flows for both systems and complete testing of cafeteria 1/17/2003 4:47:38 PM
FIR-Aging Inspection1/9/20031/9/20031/9/2003 NR
DetailsRick Jackson
talked to Alarmco and they will schedule for next week 1/9/2003 12:30:20 PM
Telephone call  10/9/2002 DONE
left mess that permit is ready
Issue permit  10/9/2002  
Plan assigned to (SAM)8/14/2002 10/8/2002 DONE
10/8/2002 15:52:43 SLR - activity updated through activity FIRA22 from case FIR02-00331.
Alarm Plan Check  10/8/2002 PASS
Plans approved based on e-mail from architect, CSHQA, indicating the school's commitment to upgrade the cafeteria "building" FA devices under a separate alarm contract, before 12/31/2002.
PLANS/APPL TAKEN TO FRONT DESK  10/8/2002 DONE
Alarm Plan Check  8/28/2002 FAIL
CONDITIONAL APPROVAL given to begin field installation prior to approval of resubmittal and issuance of the FA permit. Review comments dicussed with and faxed to Alan @ Alarmco.
Application received  8/14/2002  
Inspection Record Card- Fire10/8/2002