Permit Information
Permit NumberFIR02-00340
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2247 E SOLITUDE CT
Project NameSPR DALE BOWDEN & MARTHA CLINE
Customer Number 
ePlanReview 
Description
To fire sprinkler for Life Safety a 3296 ft/2, (1st floor - 2283 ft/2, 2nd floor - 1013 ft/2), single family two story single-family dwelling (includes the 752 ft/2 three car garage attached occupant walls). This lot is within a hillside area and is subject to the hillside ordinances. Class "A" roof system and 30 ft. defensible space will be maintained. This structure will require the installation of a NFPA 13D (Modified) fire sprinkler system. The fire sprinkler flow alarm shall be interconnected to the required residence smoke detection system. All fire sprinkler work and related (which includes dual service water supply, backflow prevention (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review notes, as regulated by the Fire Department. This permit is attached to: BLD02-01130.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20031/27/20031/27/2003APASS
DetailsTroy Cobbley
john ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
DOC - Permit Finaled1/27/20031/27/20031/27/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 1/27/2003 10:11:52 AM
INSP-Sprinkler Rough-in10/7/200210/7/200210/7/2002PPART
DetailsRick Jackson
###-#### okay to cover 10/7/2002 3:01:46 PM
INSP-Sprinkler Rough-in/Hydro10/3/200210/4/200210/4/2002AFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Marsha Smylie tenting not wide enough nor secure in all areas where plastic is used for tenting; need nail plates where pipe is vertical in stud cavities 10/4/2002 1:49:02 PM
INSP-Sprinkler Rough-in9/18/20029/19/20029/19/2002AFAIL
DetailsTroy Cobbley
rough-in of the overhead piping is ok. sprinklers need to be added in the storage space near the top of the stairs. No other items such as the riser or control valves under the floor have been looked at. 9/19/2002 3:16:43 PM 9/19/2002 3:16:59 PM
Inspection Record Card- Fire8/20/2002 8/20/2002 DONE
Telephone call  8/20/2002 DONE
permit ready and fees due
Issue permit  8/20/2002 DONE
Sprinkler Plan Check8/15/2002 8/20/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/20/2002 DONE
DetailsBill Alexander
Plan assigned to (Bill)8/15/2002 8/20/2002 DONE
Application received  8/15/2002  
Case Summary    DONE