Permit Information
Permit NumberFIR02-00348
StatusFinaled
Name M2 AUTOMATION
Site Address 300 E MALLARD DR
Project NameLake Point
Customer Number 
ePlanReview 
Description
To replace the existing Simplex 2100 fire alarm control panel with a new EST fire alarm panel. Expand upon the existing zones to provide better zone definition for the owner and fire personnel. Separate 1st, 2nd & 3rd floor elevator lobby smoke detectors from the existing general floor zones and provide separate elevator lobby zones with primary and alternate floor recall smoke detection only. Remove existing sprinkling system PIV & water valve from the sprinkler flow zone. Provide separate sprinkler flow alarm zone, PIV and water valve supervisory zones. Remove existing rooftop unit duct detectors and exhaust fan detector from the 3rd floor zone. Provide separate zone for rooftop unit duct detectors and exhaust fan smoke detector. Replace the existing smoke detectors with EST compatible smoke detectors. Replace the existing corridor 16 GA wire and audible/visual devices with 14 GA wire and synchronized audible/visual devices using temporal evacuation patern. Provide 60 hours battery backup and 5 min. alarm notification at the new FACP. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Agreement of Future work10/28/200210/28/20054/3/2003 DONE
Agree to upgrade alarm system completely by end of 2005.
INSP-Alarm Testing4/2/20034/3/20034/3/2003APASS
DetailsRick Jackson
Rick will 8am work for you? Call me if there is a conflict. Thanks Mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman
DOC - Permit Finaled4/3/20034/3/20034/3/2003APASS
DetailsRick Jackson
Finaled by inspector at 4/3/2003 8:02:57 AM
INSP-Alarm Testing1/8/20031/10/20031/10/2003PFAIL
DetailsRick Jackson
Rick at 1:00 PM if Possible
Thanks Mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman need shunt trip for elevator shutdown; change maps to reflect combining zone 8 to 6 1/10/2003 3:53:12 PM
Issue permit  12/2/2002 DONE
Alarm Plan Check11/29/2002 11/29/2002 PASS
DetailsSam Rogers
Plans approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  11/29/2002 DONE
DetailsSam Rogers
Inspection Record Card- Fire11/29/2002 11/29/2002 DONE
Plan assigned to (SAM)8/21/2002 11/29/2002 DONE
11/29/2002 13:22:39 430 - activity updated through activity FIRA22 from case FIR02-00348.
Plan resubmittals received  11/18/2002 DONE
Alarm Plan Check9/10/2002 9/10/2002 FAIL
DetailsSam Rogers
Plans failed. Review comments faxed to contractor.
Application received  8/21/2002