Permit Information
Permit NumberFIR02-00349
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameSPR HP #7 DIGITAL PRESS TEST
Customer Number 
ePlanReview 
Description
(HP BLDG #7-1ST FLR-DIGITAL PRESS TESTING) To relocate and add fire sprinklers within a 1,665 ft/2 remodel portion of an existing open office area, of which creates four new rooms surrounded by full height walls. These rooms are mechanical workrooms for support and testing new printer products manufactured by HP. The new test room's area adjacent to DP Lab in the northeast corner of the 1st floor. Fire sprinkler modifications are related to new non-combustible framing with sheetrock covering, a suspended ceiling grid system. This building is fully sprinklered. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-01300.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/23/20029/23/20029/23/2002PPASS
DetailsTroy Cobbley
fire sprinkler finaled 9/23/2002 3:00:12 PM
DOC - Permit Finaled9/23/20029/23/20029/23/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 9/23/2002 3:00:21 PM
Sprinkler Plan Check9/6/2002 9/6/2002 PASS
DetailsBill Alexander
Provided revised plan of as-built with letter for TVFP taking responsibility of OH-2 density requirements, even though design is deficient for OH pipe schedule as submitted.
Telephone call  9/6/2002 DONE
Called Troy Cobley to accept revised plan/installation meeting letter as stated and attached. (Put copy in mail box).
INSP-Final Inspection9/4/20029/5/20029/5/2002AFAIL
DetailsTroy Cobbley
too many heads on 1 1/4" branchline 9/5/2002 8:28:00 AM
INSP-Final Inspection9/3/20029/3/20029/3/2002PFAIL
DetailsTroy Cobbley
sprinkler contractor did not address note #1 for the 3/4" orfice heads in a pipe scheduled system 9/3/2002 4:19:14 PM
Plan assigned to (Bill)8/21/2002 8/29/2002 DONE
8/29/2002 08:53:11 JWA - activity updated through activity FIRA22 from case FIR02-00349.
Sprinkler Plan Check8/21/2002 8/29/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/29/2002 DONE
DetailsBill Alexander
Inspection Record Card- Fire8/29/2002 8/29/2002 DONE
Telephone call  8/29/2002 DONE
PERMIT READY AND FEES DUE
Inspection Record Card- Fire8/29/2002 8/29/2002 DONE
Issue and Print Permit  8/29/2002 DONE
Application received  8/21/2002  
Case Summary    DONE