INSP-Final Inspection | 10/28/2002 | 10/28/2002 | 10/28/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 10/28/2002 | 10/28/2002 | 10/28/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/28/2002 3:08:42 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/25/2002 | 9/26/2002 | 9/26/2002 | A | PART |
Rick Jackson
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie will reinspect when fire proofing is completed to verify that heads are operational and not covered with fireproofing 9/26/2002 9:38:27 AM
|
INSP-Conference | 9/16/2002 | 9/16/2002 | 9/16/2002 | A | PART |
Rick Jackson
|
|
|
met with Scott Apple and requested Bill ALexander to check this work out; all agree that webbing must be cleaned better or remove webbing
|
Sprinkler Plan Check | 9/6/2002 | | 9/11/2002 | | PASS |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 9/11/2002 | | 9/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 9/11/2002 | | DONE |
|
|
|
permit ready and fees due
|
Issue permit | | | 9/11/2002 | | DONE |
|
|
|
|
Application received | | | 9/6/2002 | | |
|
|
|
|
Sprinkler Plan Check | 8/29/2002 | | 8/20/2002 | | FAIL |
Bill Alexander
|
|
|
Plans lack details of intent, including truss information, elevation. Calcs lack required 5% cushion.
|
Plan assigned to (Bill) | 9/6/2002 | | | | |
|
|
|
|