INSP-Final Inspection | 8/26/2004 | 8/27/2004 | 8/27/2004 | A | PASS |
Troy Cobbley
|
|
|
fire alarm finaled. The single horn/strobe does not sound in a code 3 (temporal). It has 5 on, silence, then 6 on. Per ADT this output cannot be changed to temporal. This is a previously approved installation. 8/27/2004 11:07:00 AM
|
DOC - Permit Finaled | 8/27/2004 | 8/27/2004 | 8/27/2004 | A | PASS |
Troy Cobbley
|
|
|
|
INSP-Final Inspection | 6/23/2004 | 6/25/2004 | 6/25/2004 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 6/23/2004 at 7:20:32 AM. Contact: ###-####. Called the above number and left message; nobody returned call; must reschedule for inspection 6/25/2004 11:38:01 AM
|
INSP-Final Inspection | 6/11/2003 | 6/12/2003 | 6/12/2003 | A | FAIL |
Troy Cobbley
|
|
|
hood operated after the second try but does not come in at the fire alarm panel. Still need to verify the map at the facp 6/12/2003 12:16:18 PM
|
INSP-Final Inspection | 12/4/2002 | 12/4/2002 | 12/4/2002 | P | FAIL |
Troy Cobbley
|
|
|
the hood in Casa Mexico did not operate and ADT needs to provide a zone map for the fire alarm system at the fire alarm panel 12/5/2002 9:39:36 AM
|
Issue and Print Permit | | | 10/14/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/24/2002 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/24/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/24/2002 | | 9/24/2002 | | DONE |
|
|
|
|
Telephone call | | | 9/24/2002 | | DONE |
|
|
|
permit ready
|
Plan assigned to (SAM) | 9/6/2002 | | 9/18/2002 | | DONE |
|
|
|
9/18/2002 15:32:24 JWA - activity updated through activity FIRA22 from case FIR02-00381.
|
Alarm Plan Check | | | 9/13/2002 | | HOLD |
|
|
|
Cannot issue FA permit until we have a sprinkler permit to tie the alarm monitoring work in Taj Mahal to, and a building permit for the new cooking hood/extiguishing system in Casa Mexico to be monitored.
No sprinkler plans have been received for Taj Mahal. Called Dave Whiting, at ADT, n/a, left message to CB with this information.
|
Application received | | | 9/6/2002 | | |
|
|
|
|