Permit Information
Permit NumberFIR02-00368
StatusFinaled
Name SYNERGY ENGINEER
Site Address 1055 N CURTIS RD
Project Namealm-ST ALS-N TOWER
Customer Number 
ePlanReview 
Description
ST ALPHONSUS-NORTH TOWER-2ND FLR/PHARMACY - To modify the existing building fire alarm system within the TI area. Modifications include adding a new NAC panel to power the a/v notification appliance circuit serving the TI area, new a/v alarm devices, a smoke detector over the NAC panel, induct detectors for smoke damper release, and temperature monitoring of refrigerated rooms.
The associated building permit (BLD 02-01256) is to remodel an existing office area of 3,962 sq.ft. located on the 2nd floor north tower for use as a pharmacy administration, receiving, breakdown, distribution & storage area for service to the overall hospital facility per approved plans on file. Work includes selective demolition and new construction of interior non-bearing, non-combustible, fire-resistive walls to create accessible restroom, conference room and work areas; install movable work station furniture; upgrade per clients needs and to meet minimum codes the electrical, plumbing, mechanical, fire-suppression & alarm system; and support facilities. NOTE: A certificate of occupancy is required for this tenant. This building is fully sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/7/200210/11/200210/11/2002APASS
DetailsTroy Cobbley
fire alarm finaled 10/11/2002 10:25:06 AM
DOC - Permit Finaled10/11/200210/11/200210/11/2002APASS
DetailsTroy Cobbley
Finaled by inspector at 10/11/2002 10:25:12 AM
Alarm Plan Check10/7/2002 10/7/2002 PASS
Resubmittal - acceptable.
Plan assigned to (SAM)9/10/2002 10/7/2002 DONE
10/7/2002 10:27:53 SLR - activity updated through activity FIRA22 from case FIR02-00368.
PLANS/APPL TAKEN TO FRONT DESK  10/7/2002 DONE
Inspection Record Card- Fire10/7/2002 10/7/2002 DONE
Telephone call  10/7/2002 DONE
permit ready and fees due
Telephone call  10/7/2002 DONE
CALLED LEFT MESSAGE FOR WES PERMIT READY 10-7-02///DLD
Issue permit  10/7/2002 DONE
Application received  9/30/2002 DONE
resubmittal received
Alarm Plan Check  9/24/2002 FAIL
Significant plan deficiencies; review comments discussed with and faxed to Paul at Synergy.
INSP-Conference9/11/20029/11/20029/11/2002ADONE
DetailsTroy Cobbley
Notified general contractor that duct detectors will need to be added for automatic shut down of atleast four hvac units that serve the common area and that that work will need to be shown on the fire alarm drawings
Application received  9/10/2002