Permit Information
Permit NumberFIR02-00374
StatusFinaled
Name FRED A MORETON & CO
Site Address 12639 W EXPLORER DR
Project Namealm-FRED A MORETON & CO
Customer Number 
ePlanReview 
Description
FRED A MORETON & CO - To install a new fire alarm system in a new building. The system will include monitoring of the fire sprinkler system, elevator recall/shunt trip functions, and duct detectors for shut down of HVAC air handlers, and audible alarm in normally occupied location.
This fire alarm permit is required for approval of the building shell permit BLD01-02513 and a tenant improvement permit, BLD02-01721.
The building shell permit BLD01-02513 is TO CONSTRUCT A NEW 23,125 SQUARE FOOT, TWO STORY OFFICE SHELL AND CORE BUILDING AND RELATED SITE IMPROVEMENT. THIS BUILDING IS CONSTRUCTED OF CONCRETE TILT-UP EXTERIOR WALLS WITH INTERIOR STEEL STRUCTURAL COLUMNS AND STEEL ROOF JOIST WITH METAL ROOF DECK. THIS BUILDING IS FULLY FIRE SPRINKLED. THE SPRINKLERS ARE USE FOR AREA INCREASE. ALL CONSTRUCTION PER THE APPROVED PLANS AND ATTACHED COMMENT LIST. THIS IS A SHELL AND CORE PERMIT ONLY. NO OCCUPANCY IS ALLOWED UNDER THIS PERMIT. SEPARATE TENANT IMPROVEMENT PERMITS ARE REQUIRED TO FINISH THIS BUILDING FOR OCCUPANCY.
The TI building permit (BLD 02-02513) is to construct a 10,600 square foot office tenant space on the 2nd floor of a 23,125 square foot 2 story building. This tenant will occupy the entire 2nd floor. Work is to include interior nonbearing walls, suspended ceilings, interior doors and windows, and interior finishes.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/24/200210/24/200210/24/2002PPASS
DetailsTroy Cobbley
fire finaled
DOC - Permit Finaled10/24/200210/24/200210/24/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 10/24/2002 2:47:56 PM
INSP-Final Inspection10/18/200210/18/200210/18/2002PFAIL
DetailsTroy Cobbley
test all fire sprinkler devices, provide in-duct detector for all fire/smoke dampers, rewire duct detector and retest over the breakroom, retest shunt trip for elevator, test all duct detectors, test pull station, verify all signals and double check all review notes 10/18/2002 4:35:00 PM
Issue permit  10/18/2002 DONE
Alarm Plan Check  10/18/2002 PASS
approved with CONDITIONS. Also, a permit fee will be charged for installing the system without a permit.
PLANS/APPL TAKEN TO FRONT DESK  10/18/2002 DONE
Plan assigned to (SAM)9/12/2002 10/18/2002 DONE
10/18/2002 08:38:44 SLR - activity updated through activity FIRA22 from case FIR02-00374.
Telephone call  10/18/2002 DONE
left mess that permit is ready
Telephone call  10/16/2002 DONE
telcon from Troy Cobbley. While doing sprinkler rough-in inspection, he noted the alarm system is being installed, with no permit/approved drawings. He issued stop work order and advised them of the double fee penalty.
Alarm Plan Check  9/26/2002 FAIL
This address does not match the address on the referenced BLD permit. Application rejected, with cover memo to provide correct information.
Application received  9/12/2002  
Inspection Record Card- Fire10/18/2002