INSP-Final Inspection | 10/24/2002 | 10/24/2002 | 10/24/2002 | P | PASS |
Troy Cobbley
|
|
|
fire finaled
|
DOC - Permit Finaled | 10/24/2002 | 10/24/2002 | 10/24/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/24/2002 2:47:56 PM
|
INSP-Final Inspection | 10/18/2002 | 10/18/2002 | 10/18/2002 | P | FAIL |
Troy Cobbley
|
|
|
test all fire sprinkler devices, provide in-duct detector for all fire/smoke dampers, rewire duct detector and retest over the breakroom, retest shunt trip for elevator, test all duct detectors, test pull station, verify all signals and double check all review notes 10/18/2002 4:35:00 PM
|
Issue permit | | | 10/18/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/18/2002 | | PASS |
|
|
|
approved with CONDITIONS. Also, a permit fee will be charged for installing the system without a permit.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/18/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 9/12/2002 | | 10/18/2002 | | DONE |
|
|
|
10/18/2002 08:38:44 SLR - activity updated through activity FIRA22 from case FIR02-00374.
|
Telephone call | | | 10/18/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Telephone call | | | 10/16/2002 | | DONE |
|
|
|
telcon from Troy Cobbley. While doing sprinkler rough-in inspection, he noted the alarm system is being installed, with no permit/approved drawings. He issued stop work order and advised them of the double fee penalty.
|
Alarm Plan Check | | | 9/26/2002 | | FAIL |
|
|
|
This address does not match the address on the referenced BLD permit. Application rejected, with cover memo to provide correct information.
|
Application received | | | 9/12/2002 | | |
|
|
|
|
Inspection Record Card- Fire | 10/18/2002 | | | | |
|
|
|
|