INSP-Final Inspection | 12/20/2002 | 12/20/2002 | 12/20/2002 | P | PASS |
Troy Cobbley
|
|
|
fire sprinklers finaled 12/20/2002 2:44:18 PM
|
DOC - Permit Finaled | 12/20/2002 | 12/20/2002 | 12/20/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 12/20/2002 2:44:34 PM
|
INSP-Final Inspection | 12/4/2002 | 12/4/2002 | 12/4/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide test to verify flow for hydraulic calcs., remove switch that shuts off power for the air compressor, provide lockout on aircompressor breaker, provide hydraulic placard 12/4/2002 2:00:28 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/13/2002 | 11/14/2002 | 11/14/2002 | A | PASS |
Troy Cobbley
|
|
|
hydro test is ok and the rough-in is ok 11/14/2002 3:55:11 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/12/2002 | 11/13/2002 | 11/13/2002 | P | PASS |
Troy Cobbley
|
|
|
24 hour air test for the dry system is ok. It lost just over a pound of pressure 11/13/2002 1:17:21 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/12/2002 | 11/12/2002 | 11/12/2002 | P | PART |
Troy Cobbley
|
|
|
24 hour air test on the dry system. The gauge reads just under 42 lbs and the clock started at 1:00 pm
|
Inspection Record Card- Fire | 10/4/2002 | | 10/4/2002 | | DONE |
|
|
|
|
Telephone call | | | 10/4/2002 | | DONE |
|
|
|
permit ready and fees due
|
Issue permit | | | 10/4/2002 | | |
|
|
|
|
Sprinkler Plan Check | 9/30/2002 | | 10/4/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/4/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 9/17/2002 | | 9/18/2002 | | DONE |
Bill Alexander
|
|
|
9/18/2002 15:32:24 JWA - activity updated through activity FIRA22 from case FIR02-00381.
|
Sprinkler Plan Check | 9/17/2002 | | 9/18/2002 | | FAIL |
Bill Alexander
|
|
|
Requires backflow prevention, backflow test connection, data on a required air compressor and revised calculations.
|
Telephone call | | | 9/18/2002 | | DONE |
|
|
|
PLANS FAILED NEED TO PICK UP
|
Application received | | | 9/17/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|