Permit Information
Permit NumberFIR02-00389
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2280 E SOLITUDE CT
Project NameSPR NGO RESIDENCE
Customer Number 
ePlanReview 
Description
NGO RESIDENCE * To install an NFPA 13D fire sprinkler system in a new 4,031 ft/2, two story single family dwelling with a 2,077 ft/2 unfinished basement. NOTE: Separate permit will be required to finish basement. The sprinkler flow alarm shall be attached to the residence smoke detection system. This lot is within a hillside area and is subject to the hillside ordinances. All fire sprinkler work and related (which includes dual service water supply and backflow prevention (provided by others), shall be per NFPA 13D, approved plans, engineered/redlined and attached review comments and conditions list, as regulated by the Fire Department. This permit is attached to: BLD02-01261. (1st floor 2,003 ft/2, 2nd floor 2,028 ft/2)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/26/20033/27/20033/27/2003APASS
DetailsRick Jackson
JOHN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
DOC - Permit Finaled3/27/20033/27/20033/27/2003PPASS
DetailsRick Jackson
Finaled by inspector at 3/27/2003 4:42:08 PM
INSP-Sprinkler Rough-in12/6/200212/9/200212/9/2002AFAIL
DetailsRick Jackson
###-#### basement is not going to get a finished ceiling, if not, then sprinklers in basement not installed per listing for CPVC 12/10/2002 10:41:24 AM
Issue permit  10/14/2002 DONE
Inspection Record Card- Fire10/14/2002 10/14/2002 DONE
Telephone call  10/14/2002 DONE
permit ready and fees due
Plan assigned to (Bill)9/27/2002 10/11/2002 DONE
10/11/2002 16:16:45 JWA - activity updated through activity FIRA22 from case FIR02-00389.
PLANS/APPL TAKEN TO FRONT DESK  10/11/2002 DONE
DetailsBill Alexander
Sprinkler Plan Check10/11/2002 10/11/2002 PASS
DetailsBill Alexander
Telephone call  10/10/2002 DONE
left mess that plans needs to be picked up-review failed
Miscellaneous action  10/10/2002 DONE
DetailsBill Alexander
Took failed plans to front desk to call and return to contractor.
Sprinkler Plan Check10/9/2002 10/10/2002 FAIL
DetailsBill Alexander
Garage-living space walls, ceiling are not fully protected.
Plans and calculations do not corelate.
Backflow devise manufacturer and model is not provided (verify pressure loss-calcs).
Miscellaneous action  10/7/2002 DONE
Took failed submittals/plans to the front desk for returning.
Sprinkler Plan Check9/30/2002 10/7/2002 FAIL
DetailsBill Alexander
Sprinkler head data submittals are obsolete. Calculation are not correct sincel using old data submittals. (Requires new submittals, with new calculations) Exposed CPVC installation in the basement does not meet minimum manufacturers installation listing requirements.
Telephone call  10/7/2002 DONE
left mess that permit was denied & needs to be picked up
Application received  9/27/2002  
Case Summary    DONE