INSP-Final Inspection | 3/26/2003 | 3/27/2003 | 3/27/2003 | A | PASS |
Rick Jackson
|
|
|
JOHN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
DOC - Permit Finaled | 3/27/2003 | 3/27/2003 | 3/27/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/27/2003 4:42:08 PM
|
INSP-Sprinkler Rough-in | 12/6/2002 | 12/9/2002 | 12/9/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### basement is not going to get a finished ceiling, if not, then sprinklers in basement not installed per listing for CPVC 12/10/2002 10:41:24 AM
|
Issue permit | | | 10/14/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/14/2002 | | 10/14/2002 | | DONE |
|
|
|
|
Telephone call | | | 10/14/2002 | | DONE |
|
|
|
permit ready and fees due
|
Plan assigned to (Bill) | 9/27/2002 | | 10/11/2002 | | DONE |
|
|
|
10/11/2002 16:16:45 JWA - activity updated through activity FIRA22 from case FIR02-00389.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/11/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 10/11/2002 | | 10/11/2002 | | PASS |
Bill Alexander
|
|
|
|
Telephone call | | | 10/10/2002 | | DONE |
|
|
|
left mess that plans needs to be picked up-review failed
|
Miscellaneous action | | | 10/10/2002 | | DONE |
Bill Alexander
|
|
|
Took failed plans to front desk to call and return to contractor.
|
Sprinkler Plan Check | 10/9/2002 | | 10/10/2002 | | FAIL |
Bill Alexander
|
|
|
Garage-living space walls, ceiling are not fully protected.
Plans and calculations do not corelate.
Backflow devise manufacturer and model is not provided (verify pressure loss-calcs).
|
Miscellaneous action | | | 10/7/2002 | | DONE |
|
|
|
Took failed submittals/plans to the front desk for returning.
|
Sprinkler Plan Check | 9/30/2002 | | 10/7/2002 | | FAIL |
Bill Alexander
|
|
|
Sprinkler head data submittals are obsolete. Calculation are not correct sincel using old data submittals. (Requires new submittals, with new calculations) Exposed CPVC installation in the basement does not meet minimum manufacturers installation listing requirements.
|
Telephone call | | | 10/7/2002 | | DONE |
|
|
|
left mess that permit was denied & needs to be picked up
|
Application received | | | 9/27/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|