Case Summary | | | 4/13/2005 | | |
|
|
|
|
INSP-Final Inspection | 11/8/2004 | 11/8/2004 | 11/8/2004 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Expired | 11/8/2004 | 11/8/2004 | 11/8/2004 | P | PASS |
Rick Jackson
|
|
|
Expired by inspector at 11/8/2004 3:10:14 PM
|
INSP-Final Inspection | 10/5/2004 | 10/7/2004 | 10/7/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/5/2004 at 3:19:20 PM. Contact: ###-####. Completed all phases of this permit; need to verify with Mary if any other submittals are needed to plan review 10/8/2004 7:58:32 AM
|
INSP-Final Inspection | 9/16/2004 | 9/17/2004 | 9/17/2004 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/16/2004 at 3:05:12 PM. Contact: ###-####. Area D with TI's okay; still need Area E and temp walkway modified for permanent storage/office use 9/17/2004 11:41:41 AM
|
INSP-Final Inspection | 9/7/2004 | 9/10/2004 | 9/10/2004 | A | CANC |
Rick Jackson
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Call when ready for changes that are needed for final 9/10/2004 11:59:16 AM
|
INSP-Final Inspection | 9/7/2004 | 9/9/2004 | 9/9/2004 | A | FAIL |
Rick Jackson
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Need additional pull at exit door to stair C in area E; need speaker/strobe in Horizon Ops and mechanical for AHU 5; as-builts needed at final to plan review; record of completion needed at final 9/9/2004 11:52:06 AM
|
Plan resubmittals received | | | 9/9/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 9/7/2004 | 9/8/2004 | 9/8/2004 | A | FAIL |
Rick Jackson
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Change descriptors (see point list/plans); Horizon Air ops area needs notification (2nd floor); will need additional time to complete testing/acceptance 9/8/2004 12:00:50 PM
|
INSP-Alarm Testing | 9/3/2004 | 9/3/2004 | 9/3/2004 | A | PART |
Rick Jackson
|
|
|
tested Area C at car rental expansion - okay; all horn/strobes operated in Phase 2 on all floors 9/3/2004 9:10:09 AM
|
Inspection Record Card- Fire | 6/17/2004 | | 6/17/2004 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/14/2004 | | DONE |
|
|
|
issued
|
Alarm Plan Check | | | 6/8/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/8/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/8/2004 | | DONE |
|
|
|
|
Telephone call | | | 6/8/2004 | | DONE |
|
|
|
left a message for Chris Willis -- permit is ready.
|
Plan resubmittals received | | | 5/27/2004 | | |
|
|
|
|
Alarm Plan Check | | | 4/22/2004 | | FAIL |
|
|
|
Resubmittal Required. Faxed comments to Chris Willis 4/22/2004
|
Plan resubmittals received | | | 4/2/2004 | | DONE |
|
|
|
|
INSP-Conference | 2/3/2004 | 2/4/2004 | 2/4/2004 | A | PASS |
Rick Jackson
|
|
|
Met with Al and reviewed custom lables with locations/room numbers - this portion of Phase I is completed and closes out any open inspection items 2/4/2004 3:03:30 PM
|
INSP-Conference | 12/30/2002 | 12/30/2002 | 12/30/2002 | A | PART |
Rick Jackson
|
|
|
met with Steve of LEA Electirc; c/n issued - need detectors installed within 5 ft of smoke/fire dampers; need access doors at all dampers; will need to verify duct detector operation with air differential pressure test per Simplex manual instructions; duct detectors are installed at some smoke/fire dampers - plans show in-duct detectors; numerous pockets in computer room ceiling which will require detectors for pre-action system 12/30/2002 11:00:43 AM
|
Issue and Print Permit | | | 10/29/2002 | | |
|
|
|
|
Plan assigned to (SAM) | 10/15/2002 | | 10/25/2002 | | DONE |
|
|
|
10/25/2002 14:22:49 430 - activity updated through activity FIRA22 from case FIR02-00411.
|
Alarm Plan Check | 10/25/2002 | | 10/25/2002 | | PASS |
Sam Rogers
|
|
|
Approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/25/2002 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 10/25/2002 | | 10/25/2002 | | DONE |
|
|
|
|
Telephone call | | | 10/25/2002 | | DONE |
|
|
|
permit ready and fees due
|
Application received | | | 10/15/2002 | | |
|
|
|
|