Permit Information
Permit NumberFIR02-00413
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 770 W AMITY RD
Project NameSPR LAKE CITY INTERNATIONAL
Customer Number 
ePlanReview 
Description
(LAKE CITY INTERNATIONAL) * To upgrade the tenants fire sprinkler system in a 10,515 ft/2 structure, which includes adding sprinklers under all overhead doors and rooms which were not protected. Also add a new extension of the same system into an attached 1,055-ft/2 wash-bay on the south side of the structure. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any other permit. (JWA)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/30/20103/30/20103/30/2010PPASS
DetailsForrest France
Aging fire sprinkler permit finaled.
FIR-Aging Inspection3/29/20103/29/20103/30/2010 DONE
DetailsForrest France
Final scheduled.
Miscellaneous action  3/12/2010 DONE
Sent email requesting project status.
INSP-Sprinkler Rough-in/Hydro12/13/200212/13/200212/13/2002PFAIL
DetailsRick Jackson
Would like to Hydro new wash bay and rough inspection for the other areas. Scott Carter is foreman on site. ###-####; Phone #: ###-#### Internet Inspection Request from: Trent Bice hydro and r/i okay; installed per plans; need spare heads; need alarm plans for sprinkler monitoring; needs knox box 12/13/2002 2:18:51 PM
Issue permit  11/19/2002 DONE
Inspection Record Card- Fire11/18/2002 11/18/2002 DONE
Telephone call  11/18/2002 DONE
PERMIT READY AND FEES DUE
Plan assigned to (Bill)10/16/2002 11/18/2002 DONE
11/18/2002 10:34:18 JWA - activity updated through activity FIRA22 from case FIR02-00413.
Sprinkler Plan Check11/12/2002 11/18/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  11/18/2002 DONE
DetailsBill Alexander
Plan resubmittals received  11/12/2002 DONE
DetailsBill Alexander
Plan assigned to (Bill)11/8/2002 11/8/2002 DONE
Sprinkler Plan Check10/17/2002 10/23/2002 FAIL
DetailsBill Alexander
Need submittal data of backflow preventer. Means shall be provided downstream of all backflow prevention valves for flow tests at system demand. Need submittal data expansion chamber. Need clarification of wall type/s where earthquake bracing shall be attached. Verify connections to the same meeting minimum code. Need clearer enlargement and clarification on section detail (with calculation nodes) between A6 and A7, (antifreeze loop). Need to show the elevation (with dimensioning) of backflow preventer. Include type of control valves and required tampering. Need existing riser section detail with some dimensioning of pertinent points and node identifications.
No roof structure construction clarification provided in existing building. Lines adding (overhead doors and near demising wall) need identified hangers and how they to be supported and attached, etc.
Miscellaneous action  10/23/2002 DONE
DetailsBill Alexander
Took submittal and review notes to front desk for calling and returning to submitter.
Telephone call  10/23/2002 DONE
called for a pick up plans failed
Application received  10/16/2002  
Case Summary    DONE