Permit Information
Permit NumberFIR02-00423
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 9950 W USTICK RD
Project NameSPR NEW HEIGHTS CHRISTIAN
Customer Number 
ePlanReview 
Description
(NEW HEIGHTS CHRISTIAN FELLOWSHIP ADDITION) To install a complete, new, wet system with an extended dry system protecting a porte-cochere, in a 17,367 ft/2 one story, Type V1hr sanctuary with classrooms, office, kitchen and narthex addition to an existing fire sprinklered building. Also included in this permit is the installation of approximately 170'-0" of 6" C-900, PVC supply main west of the structure, starting at the property line off Jullion St., running east, and into the new facilities outside accessible Riser room, #112. The new addition must be fully fire sprinklered for substitution of the one-hour construction. All fire sprinkler system installation work and equipment, materials and appurtenance shall comply with NFPA 13?1999, 24-1995, 72-1999, and attached review comment and conditions list; as regulated by the Fire Chief. These notes, permit and fire Inspection Card are required to be on site as a condition of this work, to provide witness of compliance verification meeting minimum code. This permit is attached to building permit: BLD02-00155.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/28/2003 DONE
Job was finaled by Troy without revised plans as requrested.
INSP-Final Inspection5/12/20035/12/20035/12/2003PPASS
DetailsTroy Cobbley
DOC - Permit Finaled5/12/20035/12/20035/12/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 5/12/2003 3:21:14 PM
INSP-Sprinkler Rough-in/Hydro5/8/20035/9/20035/9/2003AFAIL
DetailsTroy Cobbley
Can not complete the fire sprinkler inspection until the fire alarm system is ready. The fire sprinkler connections to the fire alarm system are the only items left to complete, dry pipe riser and wet riser. 5/9/2003 11:29:27 AM
INSP-Final Inspection5/7/20035/8/20035/8/2003AFAIL
DetailsTroy Cobbley
Too many items wrong to list. see correction notice 5/8/2003 3:06:59 PM
INSP-Sprinkler Rough-in/Hydro5/7/20035/7/20035/7/2003PPART
DetailsTroy Cobbley
Started the 24 hour test on the dry system at 1:30. Guage is at 45 psi
PLANS/APPL TAKEN TO FRONT DESK  5/1/2003 DONE
DetailsBill Alexander
Resubmittals
Inspection Record Card- Fire5/1/2003 5/1/2003 DONE
Telephone call  5/1/2003 DONE
permit ready
Issue permit  5/1/2003 DONE
Sprinkler Plan Check4/30/2003 5/1/2003 PASS
DetailsBill Alexander
Fire sprinkler plan/installation revision. (faxed) Need full sized sheets.

Troy passed off without revised plans.
Plan resubmittals received  4/30/2003 DONE
DetailsBill Alexander
Fire sprinkler plan/installation revisions.
INSP-Sprinkler Rough-in/Hydro4/8/20034/8/20034/8/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/8/2003 at 8:13:02 AM. r/i of sanctuary - head has baggie and one head painted - see plans for exact locations 4/8/2003 4:02:39 PM
INSP-Sprinkler Rough-in/Hydro4/7/20034/7/20034/7/2003PPART
DetailsTroy Cobbley
See on site approved plans for locations to add upright heads and eq bracing. Other areas still need rough-in inspection 4/7/2003 12:15:41 PM
INSP-Sprinkler Rough-in/Hydro3/12/20033/13/20033/13/2003APART
DetailsTroy Cobbley
sprinkler piping is ok to cover in rooms marked on the job site approved plans. Upright sprinkler heads to be added above the mens restroom 3/13/2003 1:36:49 PM
INSP-Sprinkler Rough-in/Hydro2/11/20032/12/20032/12/2003APART
DetailsTroy Cobbley
Front canopy piping is OK to cover 2/12/2003 8:46:59 AM
Inspection Record Card- Fire11/19/2002 11/19/2002 DONE
Issue and Print Permit  11/19/2002 DONE
Plan assigned to (Bill)10/24/2002 11/18/2002 DONE
11/18/2002 17:01:50 JWA - activity updated through activity FIRA22 from case FIR02-00423.
Sprinkler Plan Check11/12/2002 11/18/2002 PASS
DetailsBill Alexander
Plan resubmittals received  11/12/2002 DONE
Sprinkler Plan Check10/24/2002 11/1/2002 FAIL
DetailsBill Alexander
Calculation problems, sprinkler head problems, need some detailed plan clarifications, etc. (Reference review)
Miscellaneous action  11/1/2002 DONE
Took failed plans to front desk for calling and returning to contractor - 2:45pm
Application DENIED  11/1/2002 DONE
plans failed return to sender
Application received  10/24/2002  
Case Summary    DONE