Permit Information
Permit NumberFIR02-00425
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 6890 S EISENMAN RD
Project Namealm-BOISE FACTORY OUTLET MALL
Customer Number 
ePlanReview 
Description
OSHKOSH B'GOSH - To install a new fire alarm system in this building to provide required offsite monitoring of the fire sprinkler system and monitoring of HVAC duct detectors for air handler shutdown.
NOTE: only the Oshkosh tenant space is being brought up to current code under this permit; per a FD approved agreement, the remaining tenant spaces will be evaluated and brought up to current fire alarm code within 3 years.
The associated building permit (BLD 02-0073) is to construct interior tenant improvements to an existing 4,580 square foot tenant space within a 32,400 square foot one story retail sales building. This tenant space was created under permit BLD02-01927 by combining two tenant spaces. Interior shell work was constructed under permit BLD02-02072. Work is to include a restroom accessible to the disabled, interior nonbearing walls, millwork, and interior finishes all per approved drawings and plan review conditions on file. This building is fire sprinklered for area increase.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/23/20031/24/20031/24/2003APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 01/23/2003 at 09:04:20. Contact: ###-####.
DOC - Permit Finaled1/24/20031/24/20031/24/2003APASS
DetailsRick Jackson
Finaled by inspector at 1/24/2003 8:12:35 AM
Agreement of Future work10/30/200211/1/20051/23/2003 DONE
See also BLDG02-02702, Bld owner agrees to upgrade Oshkash fire alarm now, and entire bldg alarm by 11-01-05 per letter of agreement on file. Pat Studdard Boise Factory Outlets.
INSP-Final Inspection1/16/20031/16/20031/17/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 01/16/2003 at 09:53:28. Contact: ###-####. signals to monitoring company aren't correct 1/17/2003 9:52:02 AM
INSP-Final Inspection1/13/20031/14/20031/14/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 01/13/2003 at 11:24:38. Contact: ###-####. need map at FACP; clarify zones to monitoring company - all zones are "alarm"; duct detectors reset by circuit breaker need location at FACP and map for breaker location 1/14/2003 4:01:05 PM
INSP-Conference12/4/200212/5/200212/5/2002PPART
DetailsRick Jackson
chris- ###-#### panel will be located in the riser room as indicated on the plans 12/5/2002 5:03:03 PM
Inspection Record Card- Fire11/6/2002 11/6/2002 DONE
Telephone call  11/6/2002 DONE
permit ready and fees due
Issue permit  11/6/2002 DONE
Alarm Plan Check  11/5/2002 PASS
PLANS/APPL TAKEN TO FRONT DESK  11/5/2002 DONE
Plan assigned to (SAM)10/24/2002 11/5/2002 DONE
11/5/2002 17:33:56 SLR - activity updated through activity FIRA22 from case FIR02-00425.
Application received  10/24/2002