Permit Information
Permit NumberFIR02-00432
StatusFinaled
Name PEAK ALARM
Site Address 8069 W FAIRVIEW AVE
Project Namealm-SHOPKO PLAZA
Customer Number 
ePlanReview 
Description
California Market - Shopko Plaza - This permit is to install a new fire alarm system. The new system will include monitoring of the fire sprinkler system, all cooking hood extinguishing systems, duct smoke detectors for HVAC air handler shut down and smoke damper release, for the entire building; plus manual pull stations and a/v annunciation within the Bearly Grown, daycare E3 occupancy area only.
The associated building permit (BLD 02-02390) is to remodel for a new retail tenant in an existing 1,821 sq. ft. space per approved plans on file. Work to include miscellaneous interior demolition work, a new accessible restroom, one-hour rated tenant demising wall interior wall infill at former door opening, interior finish, new walk-in cooler, fire sprinkler work, plumbing work, and electrical work. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for area increase.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/21/200311/21/200311/21/2003PPASS
DetailsTroy Cobbley
finaled 7-3-2003
DOC - Permit Finaled11/21/200311/21/200311/21/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/21/2003 12:16:01 PM
INSP-Final Inspection7/2/20037/3/20037/3/2003PFAIL
DetailsTroy Cobbley
Project not ready for a final inspection yet. Underground supply flush was OK though 7/3/2003 4:06:59 PM
INSP-Final Inspection6/30/20036/30/20036/30/2003PFAIL
DetailsTroy Cobbley
Install wiring connections in devices or boxes per NFPA 70 for all fire alarm devices 6/30/2003 3:04:39 PM
INSP-Final Inspection6/4/20036/5/20036/5/2003AFAIL
DetailsTroy Cobbley
Provide knox box, provide sign on fire alarm/riser door, clean up all duct detector wiring, rotate sample tube in duct detector in daycare(zone 128), provide filter for duct detector in Joey's Seafood, repair wiring and test hood in the Mongolian BBQ. 6/5/2003 11:07:33 AM
INSP-Final Inspection6/3/20036/4/20036/4/2003APART
DetailsTroy Cobbley
Started the inspection. Was not able to finish. To be continued tomorrow. 6/4/2003 11:17:04 AM
INSP-Final Inspection5/29/20035/30/20035/29/2003PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 5/29/2003 at 9:38:27 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 29 2003 3:21PM.
INSP-Final Inspection5/23/20035/28/20035/27/2003PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 5/23/2003 at 2:41:24 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 27 2003 4:20PM.
INSP-Alarm Testing5/15/20035/16/20035/16/2003APART
DetailsTroy Cobbley
The duct smoke detector over Basilio's restraunt that was previously not working now functions correctly 5/16/2003 10:30:17 AM
INSP-Alarm Testing5/9/20035/9/20035/9/2003PFAIL
DetailsTroy Cobbley
North hvac unit in the Basilio's restraunt would not operate. It is locked out until it can be repaired and tested. Smoke detector over panel, battery troubles, phone lines and pull station have been tested. No other items tested. This initial test was just to get the restraunt a temp occupancy. The main inspection to be called in next week. 5/9/2003 2:47:53 PM
Issue permit  2/12/2003 DONE
Telephone call  2/10/2003 DONE
Telcon with Dave Miller. The day care has a 1-hour occupancy separation around it and existing pull stations at all its exits. Agreed to accept the proposed Phase 1 plan, and not require Phase 2 or 3 or manual pulls and a/v outside the daycare occupany.
Alarm Plan Check  2/10/2003 PASS
resubmittal acceptable without Phase 2 and 3 as shown on plans, per FD approval and interpretation of IFC requirements.
PLANS/APPL TAKEN TO FRONT DESK  2/10/2003 DONE
Inspection Record Card- Fire2/10/2003 2/10/2003 DONE
Telephone call  2/10/2003 DONE
permit ready and fees due
Plan assigned to (SAM)11/6/2002 2/10/2003 DONE
2/10/2003 16:05:50 SLR - activity updated through activity FIRA22 from case FIR02-00432.
Plan resubmittals received  1/31/2003 DONE
discussed with Pat McKeegan; he has written Dave Miller proposing use of the IFC and his (McKeegan's) interpretation of its requirements to the new FA system. I will hold off doing a plan review of theis resubmittal until an answer is received from Dave Miller on FD's reply, specifically regarding extent of a/v alarms and pull stations.
Alarm Plan Check  11/29/2002 PEND
Delayed upgrade approved by Fire Dept in conjuction with a TOC approval for BLD02-02390. New alarm plans to be submitted after details of the upgrade program are determined by Feb 28, 2002.
INSP-Alarm Testing11/27/200211/27/200211/27/2002ANR
DetailsTroy Cobbley
A temporary occupancy was given with Dave Millers permission for the California Marketplace TI until the fire alarm system has been permited and inspected. The owner has until 2-28-03 to complete work. See letter dated 11-21-02.
Alarm Plan Check  11/14/2002 FAIL
written review faxed to Peak and to Pet Conlon, Collier's Int'l.
Telephone call  11/13/2002 DONE
Telcon with Pete Conlon, Property mgr. They have hired Jim Falk, Apex Engineering, to review our comments and prepare a new FA system design. Fax a copy of our review to Pete for his use.
Alarm Plan Check  11/8/2002 FAIL
Plans have major deficiencies. An E3/125 occupancy tenant necessitates the "builidng have a manual alarm system; improper method shown for release of smoke dampers; separation from contiguous Shopco "building" not indicated. These deficiencies discussed with Steve Larson, Peak Alarm 11/8; he will discuss with Pete Conlon Property Mgr. Written review to be sent out next week.
Telephone call  11/8/2002 DONE
Called Steve Larson to advise of plans deficiencies; written review comments to be sent out next week.
Application received  11/6/2002