Case Summary | | | 8/6/2004 | | |
|
|
|
|
INSP-Final Inspection | 5/19/2003 | 5/19/2003 | 5/19/2003 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 5/19/2003 | 5/19/2003 | 5/19/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/19/2003 3:52:17 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/26/2003 | 3/26/2003 | 3/26/2003 | P | PART |
Rick Jackson
|
|
|
ADAM; Phone #: ###-#### Internet Inspection Request from: Darla Downs hydro okay on overhead and underground 3/26/2003 4:00:53 PM
|
INSP-Supply line flush | 3/17/2003 | 3/19/2003 | 3/19/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/17/2003 at 2:16:03 PM. Contact: ###-####. flush okay; sprinkler heads painted in office area 3/19/2003 10:11:33 AM
|
INSP-Conference | 1/23/2003 | 1/24/2003 | 1/23/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/23/2003 at 13:01:06. Contact: ###-####. completed UG cover on 1/23 1/23/2003 2:47:55 PM
|
INSP-Sprinkler Rough-in | 1/23/2003 | 1/23/2003 | 1/23/2003 | P | PART |
Rick Jackson
|
|
|
underground complete; okay to cover
|
INSP-Conference | 12/19/2002 | 12/19/2002 | 12/19/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/19/2002 at 09:19:07. Contact: ###-####. conference about UG 12/19/2002 3:49:35 PM
|
INSP-Sprinkler Rough-in | 12/19/2002 | 12/19/2002 | 12/19/2002 | P | PART |
Rick Jackson
|
|
|
UG r/i okay; stub out from building
|
Inspection Record Card- Fire | 12/17/2002 | | 12/17/2002 | | DONE |
|
|
|
|
Telephone call | | | 12/17/2002 | | DONE |
|
|
|
CALLED 12-17-02
|
Issue and Print Permit | | | 12/17/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/7/2002 | | 12/16/2002 | | DONE |
|
|
|
12/16/2002 14:54:31 JWA - activity updated through activity FIRA22 from case FIR02-00436.
|
Alarm Plan Check | 12/10/2002 | | 12/16/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/16/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 12/10/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/26/2002 | | 12/9/2002 | | FAIL |
Bill Alexander
|
|
|
1. Where branch lines are larger than 2", the fire sprinkler shall be supplied by a riser nipple to elevate the sprinkler 13" for 2½" pipe. These dimensions shall be measured from the centerline of the pipe to the sprinkler deflector. NFPA 13:5-10.5.2.3)
2. Provide revised area "A" calculations incorporating the tee, riser nipple and elevation differences.
3. Provide forward flow test piping and appurtenance to meet the requirements for 10-2.6 with provision addressed in 5-15.4.6.1*
4. Sprinkler data for Model G XLO is "Bulletin 129E". This is not a current data submittal for this manufacturers sprinkler head. Package must include the current data submittals of sprinkler heads installing.
5. Provide location of required flexible couplings for mains addressed NFPA 13:6-4.2. (NFPA 13:8-1.1.1 (39).
6. Copy/File Room #104 would appear to be classified as OH-1 and spacing of sprinkler shall reflect minimum spacing of the same requirement.
7. Provide and identify an approved relief valve, set to operate at a maximum 175 psi on the riser. (NFPA 13:4-1.2)
8. Provide and identify an inspectors test in this facility.
|
Miscellaneous action | | | 12/9/2002 | | DONE |
|
|
|
Plans to be returned to submiter for resubmittals of meeting minimum code.
|
Plan resubmittals received | | | 11/26/2002 | | DONE |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 11/14/2002 | | DONE |
|
|
|
Received a call from Brodie indicating he wants to put a hold on this plan review untill further notice!
|
Sprinkler Plan Check | 11/7/2002 | | 11/14/2002 | | CANC |
Bill Alexander
|
|
|
On hold per Brodie Stenquest telephone call, 11/14/02, 10:00am. New plans coming.
|
Application received | | | 11/7/2002 | | |
|
|
|
|