Permit Information
Permit NumberFIR02-00437
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 S FEDERAL WAY
Project NameSPR MICRON FAB 1-(UNDERFLOOR)
Customer Number4440
ePlanReview 
Description
MICRON FAB 1-(UNDERFLOOR) * To install added fire sprinkler protection under-floor of a (unidentified) Fabrication room. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any known building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/10/20037/10/20037/10/2003PPASS
DetailsRick Jackson
DOC - Permit Finaled7/10/20037/10/20037/10/2003PPASS
DetailsRick Jackson
Finaled by inspector at 7/10/2003 1:47:54 PM
INSP-Final Inspection7/9/20037/9/20037/9/2003PPART
DetailsRick Jackson
WAYNE; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie it now has provisions to test the flow switch and Dan will schedule a test 7/9/2003 3:15:52 PM
INSP-Sprinkler Rough-in/Hydro6/30/20036/30/20036/30/2003PFAIL
DetailsRick Jackson
This job has already be inspected, we needed a fire alarm permit, which we haved received.; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino need way to test new flow switch 6/30/2003 3:25:54 PM
Issue permit  4/15/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  4/14/2003 DONE
DetailsBill Alexander
Telephone call  4/14/2003 DONE
called 4-14-03
Plan resubmittals received  4/11/2003 DONE
DetailsBill Alexander
Miscellaneous action  4/10/2003 DONE
Flow switch not shown and a means for testing of the same not provided. Emailed Jerry O'Neal for addendum update return attachment by fax is OK.
Plan resubmittals received  4/8/2003 DONE
for Bill Alexander
INSP-Final Inspection3/12/20033/13/20033/13/2003AFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Wayne Berry resubmittal required; need alarm plans for addition of flow switch 3/13/2003 4:14:26 PM
FIR-Aging Inspection2/20/20032/20/20032/20/2003 PART
DetailsRick Jackson
e-mailed Dan B to forward message to responsible party that I need a status of this project 2/20/2003 10:47:07 AM
Issue and Print Permit  11/21/2002 DONE
Inspection Record Card- Fire11/20/2002 11/20/2002 DONE
Telephone call  11/20/2002 DONE
PERMIT READY AND FEES DUE
Plan assigned to (Bill)11/7/2002 11/19/2002 DONE
11/19/2002 14:53:17 JWA - activity updated through activity FIRA22 from case FIR02-00437.
Sprinkler Plan Check11/12/2002 11/19/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  11/19/2002 DONE
DetailsBill Alexander
Application received  11/7/2002  
Case Summary    DONE
Sprinkler Plan Check4/8/2003   PEND
DetailsBill Alexander
4/10/03 - Original plan modification which includes a flow switch.