Miscellaneous action | | | 3/12/2010 | | DONE |
|
|
|
Sent email requesting project status.
|
Final inspection | | | 5/29/2009 | | DONE |
|
|
|
Permit was finaled on 05-09-09 by inspector 325
|
Meeting | | | 11/27/2007 | | DONE |
|
|
|
Reviewed project status with Mike Timmerman. He willl follow up with Bob Archibald to get remaining items resolved and permit finaled.
|
INSP-Final Inspection | 3/6/2003 | 3/6/2003 | 3/6/2003 | A | FAIL |
Rick Jackson
|
|
|
sprinkler head at 7 ft level in east comm room; ceiling height requires removal of this head as there are two at ceiling height; need timeline for correcting standpipe interconnection and sprinklering all unsprinklered areas as requested on plan review notes
|
INSP-Sprinkler Rough-in/Hydro | 12/20/2002 | 12/20/2002 | 12/20/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/20/2002 at 09:51:56. Contact: ###-####. overspaced in several rooms - identified on plans and c/n; hangers needed within 1 foot from end of pipe 12/20/2002 5:30:56 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/19/2002 | 12/19/2002 | 12/19/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/19/2002 at 08:39:56. Contact: ###-####.
|
Inspection Record Card- Fire | 12/2/2002 | | 12/2/2002 | | DONE |
|
|
|
|
Telephone call | | | 12/2/2002 | | DONE |
|
|
|
called 12-2-02
|
Issue permit | | | 12/2/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/8/2002 | | 12/2/2002 | | DONE |
|
|
|
12/2/2002 11:09:42 JWA - activity updated through activity FIRA22 from case FIR02-00439.
|
Sprinkler Plan Check | 11/21/2002 | | 12/2/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/2/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 11/21/2002 | | 11/21/2002 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/21/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 11/12/2002 | | 11/20/2002 | | FAIL |
Bill Alexander
|
|
|
A. No existing design limits/information provided on the plans.
B. No hanger attachment information provided.
C. Verification of proposed use of appurtenance, which was not addressed.
|
Telephone call | | | 11/20/2002 | | DONE |
|
|
|
Faxed copy of failed review.
|
Miscellaneous action | | | 11/20/2002 | | DONE |
|
|
|
Took failed plans to front desk for calling and returning for corrections.
|
Miscellaneous action | | | 11/15/2002 | | DONE |
|
|
|
Inspected first floor and found Treasure Valley working without a valvid permit. Double fees and pre-citation shall be imposed.
|
Application received | | | 11/8/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|