Permit Information
Permit NumberFIR02-00442
StatusExpired
Name BUILDING SHELL REMODEL
Site Address 818 & 822 W IDAHO ST
Project NameSPR BLD SHELL REM. BLOCK 44
Customer Number 
ePlanReview 
Description
(BUILDING SHELL REMODEL) To modify an existing historic building. To install fire sprinkler on the west side of the basement with which includes include 2 restrooms, 2 basement stairways and 2 second floor stairways. There are structural upgrades to the building, which involve wood joists, steel columns, steel beams, and a steel braced frame. Only a portion of the basement will be fire sprinklered. The basement fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list; as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-00542.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference3/16/20103/17/20103/17/2010PDONE
DetailsForrest France
Permit expired- see scope of work completed for subsequent permits at this building.
DOC - Permit Expired  3/17/2010 DONE
DetailsTisha Gallop
permit expired per Forrest France
FIR-Aging Inspection3/15/20103/15/20103/16/2010ADONE
DetailsForrest France
See FIR07-00737 for same scope of overhead work completed- permit okay to expire.
Miscellaneous action  3/12/2010 DONE
Asked inspector to visit site
INSP-Sprinkler Rough-in12/11/200212/11/200212/11/2002PPART
DetailsRick Jackson
UNDERGROUND COVER ###-#### CALL FIRST okay to cover; recoated the rods, etc with mastic; will need info on TJI hanger infor per manufacturers listing 12/11/2002 4:10:34 PM
INSP-Sprinkler Rough-in12/10/200212/10/200212/10/2002PNR
DetailsRick Jackson
CALL BRUCE FIRST; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung not ready; will reschedule 12/10/2002 4:08:32 PM
Issue and Print Permit  12/4/2002 DONE
Inspection Record Card- Fire12/2/2002 12/2/2002 DONE
Telephone call  12/2/2002 DONE
permit ready and fees due
Sprinkler Plan Check11/27/2002 12/2/2002 PASS
DetailsBill Alexander
Sprinkler Plan Check11/22/2002 11/27/2002 FAIL
DetailsBill Alexander
Calculations have one sprinkler calced? Nodes don't correlate.
Miscellaneous action  11/27/2002 DONE
Returned submittal package to submitter for corrections.
Plan resubmittals received  11/27/2002 DONE
DetailsBill Alexander
Calculations.
Plan resubmittals received  11/22/2002 DONE
To Bill A.
Sprinkler Plan Check11/13/2002 11/21/2002 FAIL
DetailsBill Alexander
a. Water supply certificate is not on the same block as permitted work shown. Fire sprinkler contractor shall provide a current water supply certification for this system, addressed at point of connection.
b. Provide addressing and clarification of required forward flow testing of backflow preventer meeting 5-15.4.6.1 with accommodations for 10-2.6.
c. Provide detailed loads of pipe and zones being braced with correlation of earthquake details and locations. NFPA 13:8-1.1.1 (39)
d. Provide and show on the plans the required inspectors test. NFPA 13:8-1.1.1 (23)
e. Plans must include thrust-restraining requirements of the underground and how this contractor intends to suppress it meeting NFPA 13/24.
f. Provide an auxiliary drain (w/signage) for this system at the riser, since this system will not drain outside.
g. Provide the formula derived incorporating 7-2.3.2.4 on the plans.
h. Provide calculation node points on "Riser Detail" section, corresponding to calculations.
i. Provide hanger location for the mains.
Miscellaneous action  11/21/2002 DONE
Took failed plans to front desk for calling and returning for corrections.
Application received  11/13/2002  
Plan assigned to (Bill)11/13/2002    
Case Summary    DONE