Permit Information
Permit NumberFIR02-00447
StatusFinaled
Name PROTEX
Site Address 11193 W EMERALD ST
Project Namealm-Fresca Mexican Foods
Customer Number 
ePlanReview 
Description
FRESCA MEXICAN FOODS - To install a new fire alarm system for this building. The system will include a new addressable FA control panel, monitoring of the partial-coverage fire sprinklers, a fire booster pump, separate detection and selective a/v alarms for the ammonia refrigeration system, and offsite alarm monitoring.

The associated building permit (BLD 02-01925) is to construct a 7,781 sq. ft. one story, Type VN, fully fire sprinklered freezer addition to the existing facility. Other work includes the upgrade of a two hour area separation wall in the existing building and all site improvements, paving and landscaping per approved plans and attachments. The existing building south of the area wall and addition will be fully fire sprinklered with the area north of the area wall to be sprinklered per the upgrade agreement with the Boise Fire Dept. Dave Miller. Fire sprinklers used for area. No occupancy can be permitted until all conditions from the Fire Dept. and Mechanical Division have been satisfied for the ammonia system per attached requirements.

The associated fire sprinkler permit FIR02-00385 to install a new 236'-0" of 8", C-900 PVC underground supply from the property line to a new 142 ft/2 Fire Pump House. To install 6", C-900 PVC underground supply from the Fire Pump House into an existing building (Room "C") for a new combination riser. To abandon the existing 6"underground supply feeding from Meadowland Drive and remove the existing remote FDC (new one to be located off the Fire Pump House). To connect the existing Double Interlock Pre-action system riser protecting the existing freezer onto the new riser supply (in Room "C"). To install a 1,500 gpm, 100 HP fire pump, controller, and pressure maintenance jockey pump, controller and related/required appurtenances and to install fire sprinkler protection throughout the entire facility. This project is Phase 1 of 3 phases; of which the final results will be to completely fire sprinkler the entire facility, meeting UBC requirements for area increase. (This building was originally constructed in Ada County and later annexed into Boise City).
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20034/23/20034/23/2003APASS
DetailsTroy Cobbley
This is Grants Cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
DOC - Permit Finaled4/23/20034/23/20034/23/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 4/23/2003 3:30:02 PM
Issue and Print Permit  4/9/2003 DONE
Alarm Plan Check  4/8/2003 PASS
DetailsSam Rogers
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  4/8/2003 DONE
DetailsSam Rogers
Inspection Record Card- Fire4/8/2003 4/8/2003 DONE
Telephone call  4/8/2003 DONE
###-####
Plan assigned to (SAM)11/15/2002 4/8/2003 DONE
4/8/2003 15:41:24 430 - activity updated through activity FIRA22 from case FIR02-00447.
Plan resubmittals received  3/25/2003  
Miscellaneous action  3/5/2003 DONE
faxed reply to Protex's request to eleiminate emergency pull stations outside theexits. Agreed to accept the pull stations be located INside the exits, to eliminate exposure to tampering by neighborhood vandals.
Alarm Plan Check  2/3/2003 FAIL
Review comments faxed to Protex per meeting 1/31/03; approval granted for installation to begin without approved plans/permit. No inspections to be done until permit and approved plans are issued.
Meeting  1/31/2003 DONE
Meeting with alarm vendor rescheduled for today. Discussed plan submittal deficiencies with Rob Ahten. He will resubmit reivsed plans. Agreed to allow installation to begin without approved plans/permit. No inspections to be done until permit and approved plans are issued.
Alarm Plan Check  1/22/2003 FAIL
Called Rob at Protex set up meeting to discuss today at 2:00 pm.
Meeting canceled due to Rob's illness; to be rescheduled.
Plan resubmittals received  1/10/2003 DONE
Alarm Plan Check  12/2/2002 FAIL
Review faxed to Protex
Application received  11/15/2002