INSP-Final Inspection | 2/24/2003 | 2/24/2003 | 2/24/2003 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 2/24/2003 | 2/24/2003 | 2/24/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/24/2003 10:16:33 AM
|
Miscellaneous action | | | 2/24/2003 | | DONE |
|
|
|
Received as-builts of second floor (added lines and heads).
|
INSP-Sprinkler Rough-in/Hydro | 12/20/2002 | 12/20/2002 | 12/20/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/20/2002 at 09:03:55. Contact: ###-####. r/i and hydro okay; need sprinklers in old computer room by PDS records 12/20/2002 5:32:20 PM
|
Inspection Record Card- Fire | 12/2/2002 | | 12/2/2002 | | DONE |
|
|
|
|
Telephone call | | | 12/2/2002 | | DONE |
|
|
|
called 12-2-02
|
Issue permit | | | 12/2/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/12/2002 | | 12/2/2002 | | DONE |
Bill Alexander
|
|
|
12/2/2002 11:35:46 JWA - activity updated through activity FIRA22 from case FIR02-00451.
|
Sprinkler Plan Check | 11/21/2002 | | 12/2/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/2/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 11/21/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 11/12/2002 | | 11/20/2002 | | FAIL |
Bill Alexander
|
|
|
A. No existing design limits/information provided on the plans.
B. No hanger attachment information provided for either floor permitted.
C. Previous permitted work entailed the use of flexible pipe/head connections. If installer is proposing to use the same appurtenance, it must also become a part of the record and included in the permits, etc. Plans are not detailed meeting NFPA 13:8-1, for allowance to proceed.
|
Telephone call | | | 11/20/2002 | | DONE |
|
|
|
Faxed copy of review.
|
Miscellaneous action | | | 11/20/2002 | | DONE |
|
|
|
Returned plans to front desk for calling and returning for corrections.
|
Miscellaneous action | | | 11/20/2002 | | DONE |
|
|
|
Walked through floor and found fire sprinkler modifications have proceeded without a valid permitting or approval. Contractor indicated that work was performed 11/15/02.
Dobule fees are impossed.
|
Application received | | | 11/12/2002 | | |
|
|
|
This permit established 11/19/2002. Original came in under BLD02-01413 with FIR02-00439 (First Floor, same building).
|