Permit Information
Permit NumberFIR02-00473
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 6300 W DENTON ST
Project NameSPR Ada County Juvenile Det.
Customer Number 
ePlanReview 
Description
Ada County Juvenile Detention Center (Entry Addition) - To add 2400 ft/2, Type II-N, single story entry addition to the Juvenile Detention Center per plans and attachments. This building is fully fire sprinklered for area. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-02287.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/6/20035/7/20035/7/2003PPASS
DetailsTroy Cobbley
Fire sprinklers finaled 5/7/2003 2:21:34 PM
DOC - Permit Finaled5/7/20035/7/20035/7/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 5/7/2003 2:21:40 PM
INSP-Final Inspection4/22/20034/23/20034/23/2003PFAIL
DetailsTroy Cobbley
TODD; Phone #: ###-#### Sprinkler heads are overspaced in the existing lobby, hangers to be attached to the top of the structure (see the detail on the approved drawings), provide eq straps on all piping in th escope of work, installation does not match approved plans. Review notes appear to state the max. head spacing to be 149 sq. ft. Pendants in the lobby exceed this. Provide approved drawings with the 1/6/03 date on them. These drawings are showing the work in the lobby area. The previous resubmittal drawings show existing heads only. The pendants installed now don't even match those locations 4/23/2003 10:13:52 AM
INSP-Final Inspection4/7/20034/7/20034/7/2003PPART
DetailsTroy Cobbley
Fire sprinklers given temp with dave millers permission. There is still some work in the lobby and a restroom that needs to be added near the lobby
INSP-Sprinkler Rough-in/Hydro3/20/20033/20/20033/20/2003PPART
DetailsRick Jackson
TERRY; Phone #: ###-#### Internet Inspection Request from: Darla Downs hydro on overhead okay 3/20/2003 4:13:14 PM
INSP-Sprinkler Rough-in/Hydro3/18/20033/18/20033/18/2003PPASS
DetailsTroy Cobbley
Sprinklers are OK to cover. Provide one additional sprinkler pendant over the security desk 3/18/2003 2:00:35 PM
Issue permit  3/10/2003 DONE
Plan resubmittals received  3/5/2003 DONE
Sprinkler Plan Check3/5/2003 3/5/2003 PASS
DetailsBill Alexander
Plan modifications (added heads).
Inspection Record Card- Fire3/5/2003 3/5/2003 DONE
Telephone call  3/5/2003 DONE
permit ready and fees due
Plan resubmittals received  3/4/2003 DONE
to Bill Alexander
Issue and Print Permit  1/24/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/20/2002 DONE
DetailsBill Alexander
Inspection Record Card- Fire12/20/2002 12/20/2002 DONE
Telephone call  12/20/2002 DONE
permit ready and fees due
Plan assigned to (Bill)11/27/2002 12/20/2002 DONE
12/20/2002 11:21:50 JWA - activity updated through activity FIRA22 from case FIR02-00473.
Sprinkler Plan Check12/16/2002 12/20/2002 PASS
DetailsBill Alexander
Miscellaneous action  12/19/2002 DONE
Took copy of 2nd submittal to front desk for calling and returning.
Telephone call  12/18/2002 DONE
DetailsBill Alexander
Problem with remote area #1 (still). Called (Tom Easton-designer) and left message to call me back in the morning.
Plan resubmittals received  12/16/2002 DONE
DetailsBill Alexander
Telephone call  12/10/2002 DONE
plans denied called to have picked up
Sprinkler Plan Check11/27/2002 12/9/2002 FAIL
DetailsBill Alexander
a. Remote test area #2 does not meet minimum requirements of NFPA 13:7-2.3. Revise, recalculate and resubmit.
b. Remote test area #2 does not meet minimum requirements of NFPA 13:5-6.2. Revise, recalculate and resubmit.
c. Cover sheet for test area #2 does not correlate with calculations provided.
d. Remote test area #2, Conference room #011 is overspaced for design provided. Does not meet NFPA 13:5?5.3.1 and 5-5.3.1.2
e. Remote test area #2, Storage room #010 appears to have a room inside of the room? Provide clarification.
f. Remote test area #1,Vestibule entry rooms #001 do not meet NFPA 13:5?5.3.1 and 5-5.3.1.2 as calculated.
g. Plan FP2 of 2, hydraulic remote summaries do not correlate with actual calculation (spacing) verified. Note: If verifying a head spacing of 256 ft/2, etc., the calculations must include pipe and fitting matching 256 ft/2 spacing.
h. General Notes #5, 6 and 7 do not apply to this project and as such, should not be addressed.
Miscellaneous action  12/9/2002 DONE
DetailsBill Alexander
Return plans to submitter for resubmittals meeting minimum code.
Application received  11/27/2002  
Case Summary    DONE