INSP-Final Inspection | 5/6/2003 | 5/7/2003 | 5/7/2003 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled 5/7/2003 2:21:34 PM
|
DOC - Permit Finaled | 5/7/2003 | 5/7/2003 | 5/7/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/7/2003 2:21:40 PM
|
INSP-Final Inspection | 4/22/2003 | 4/23/2003 | 4/23/2003 | P | FAIL |
Troy Cobbley
|
|
|
TODD; Phone #: ###-#### Sprinkler heads are overspaced in the existing lobby, hangers to be attached to the top of the structure (see the detail on the approved drawings), provide eq straps on all piping in th escope of work, installation does not match approved plans. Review notes appear to state the max. head spacing to be 149 sq. ft. Pendants in the lobby exceed this. Provide approved drawings with the 1/6/03 date on them. These drawings are showing the work in the lobby area. The previous resubmittal drawings show existing heads only. The pendants installed now don't even match those locations 4/23/2003 10:13:52 AM
|
INSP-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 | P | PART |
Troy Cobbley
|
|
|
Fire sprinklers given temp with dave millers permission. There is still some work in the lobby and a restroom that needs to be added near the lobby
|
INSP-Sprinkler Rough-in/Hydro | 3/20/2003 | 3/20/2003 | 3/20/2003 | P | PART |
Rick Jackson
|
|
|
TERRY; Phone #: ###-#### Internet Inspection Request from: Darla Downs hydro on overhead okay 3/20/2003 4:13:14 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/18/2003 | 3/18/2003 | 3/18/2003 | P | PASS |
Troy Cobbley
|
|
|
Sprinklers are OK to cover. Provide one additional sprinkler pendant over the security desk 3/18/2003 2:00:35 PM
|
Issue permit | | | 3/10/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/5/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/5/2003 | | 3/5/2003 | | PASS |
Bill Alexander
|
|
|
Plan modifications (added heads).
|
Inspection Record Card- Fire | 3/5/2003 | | 3/5/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/5/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan resubmittals received | | | 3/4/2003 | | DONE |
|
|
|
to Bill Alexander
|
Issue and Print Permit | | | 1/24/2003 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/20/2002 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 12/20/2002 | | 12/20/2002 | | DONE |
|
|
|
|
Telephone call | | | 12/20/2002 | | DONE |
|
|
|
permit ready and fees due
|
Plan assigned to (Bill) | 11/27/2002 | | 12/20/2002 | | DONE |
|
|
|
12/20/2002 11:21:50 JWA - activity updated through activity FIRA22 from case FIR02-00473.
|
Sprinkler Plan Check | 12/16/2002 | | 12/20/2002 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 12/19/2002 | | DONE |
|
|
|
Took copy of 2nd submittal to front desk for calling and returning.
|
Telephone call | | | 12/18/2002 | | DONE |
Bill Alexander
|
|
|
Problem with remote area #1 (still). Called (Tom Easton-designer) and left message to call me back in the morning.
|
Plan resubmittals received | | | 12/16/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 12/10/2002 | | DONE |
|
|
|
plans denied called to have picked up
|
Sprinkler Plan Check | 11/27/2002 | | 12/9/2002 | | FAIL |
Bill Alexander
|
|
|
a. Remote test area #2 does not meet minimum requirements of NFPA 13:7-2.3. Revise, recalculate and resubmit.
b. Remote test area #2 does not meet minimum requirements of NFPA 13:5-6.2. Revise, recalculate and resubmit.
c. Cover sheet for test area #2 does not correlate with calculations provided.
d. Remote test area #2, Conference room #011 is overspaced for design provided. Does not meet NFPA 13:5?5.3.1 and 5-5.3.1.2
e. Remote test area #2, Storage room #010 appears to have a room inside of the room? Provide clarification.
f. Remote test area #1,Vestibule entry rooms #001 do not meet NFPA 13:5?5.3.1 and 5-5.3.1.2 as calculated.
g. Plan FP2 of 2, hydraulic remote summaries do not correlate with actual calculation (spacing) verified. Note: If verifying a head spacing of 256 ft/2, etc., the calculations must include pipe and fitting matching 256 ft/2 spacing.
h. General Notes #5, 6 and 7 do not apply to this project and as such, should not be addressed.
|
Miscellaneous action | | | 12/9/2002 | | DONE |
Bill Alexander
|
|
|
Return plans to submitter for resubmittals meeting minimum code.
|
Application received | | | 11/27/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|