Permit Information
Permit NumberFIR02-00475
StatusFinaled
Name SYNERGY ENGINEER
Site Address 1055 N CURTIS RD
Project Namealm-ST ALS-S TOWER
Customer Number 
ePlanReview 
Description
SARMC S. TOWER, 5TH FL. PATIENT CARE UNIT - To add complete automatic and manual fire alarm coverage in the 5th floor remodel area, connected to the existing networked facility fire alarm system. Coverage shown on plans includes, but is not limited to, manual pull stations, area smoke detection, elevator recall, release of door hold-opens, smoke detectors for HVAC air handler shutdown and release of smoke dampers, and a/v annunciation.
The associated building permit (BLD 02-00730) is to remodel the remaining 16,645 sq.ft.East portion of the fifth floor area to serve as a 41 bed Nursing Unit for general medical & surgical care per approved plans on file. Work to include selective demolition; construction of new interior, non-bearing, non-combustible, fire-resistive walls to create new patient rooms, nurses stations and support areas; to upgrade electrical, plumbing, mechanical, fire suppression and alarm systems to meet tenant needs and comply with current adopted codes.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/200311/7/200311/7/2003PPASS
DetailsTroy Cobbley
fire alarm finaled
DOC - Permit Finaled11/7/200311/7/200311/7/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/7/2003 1:09:28 PM
INSP-Final Inspection10/28/200310/28/200310/28/2003PFAIL
DetailsTroy Cobbley
provide updated map, repair the two strobes, and relocate the strobe that is too far from the north side double doors
PLANS/APPL TAKEN TO FRONT DESK  10/28/2003 DONE
CHANGE STATUS TO (ISS)  10/28/2003 DONE
per sam issued with fir 02-00474 on -1/28/03
Alarm Plan Check10/28/2003 1/27/2003 PASS
Resubmittal acceptable; resubmitted plan and review combined with FIR02-00474; separate permits required due to separate building permits.
Alarm Plan Check  12/31/2002 FAIL
Faxed review comments to Synergy.
Plan resubmittals received  12/13/2002 DONE
Alarm Plan Check  12/6/2002 FAIL
Plans grossly deficient; only partial review conducted. Comments faxed to Synergy, designer.
Application received  11/27/2002  
Plan assigned to (SAM)11/27/2002    
no fee due
Plan assigned to (SAM)12/13/2002