Permit Information
Permit NumberFIR02-00476
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 6300 W DENTON ST
Project Namealm-Ada County
Customer Number 
ePlanReview 
Description
Ada County Juvenile Detention Center - To modify the existing building fire alarm system within the TI area. Work includes relocating an existing annunciator panel and adding area smoke detection, duct detectors for fire smoke damper release and for HVAC air handler shut down, a/v annunciation.
The associated building permit (BLD 02-02287) is to add a 2400 sq.ft., Type IIN, single story entry addition to the Juvenile Detention Center per approved plans and attachments DRH02-00135. This building is fully fire sprinklered for area.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing6/24/20036/25/20036/25/2003APASS
DetailsRick Jackson
Rick,
This is the project that we spoke about yesterday. We would like to have you on-site at 7:00 am if at all possible, in order to be out of the county's way when they are ready to begin their day. If there are any problems, please call me on my cell ###-####, or at the office ###-####. Thank you.; Phone #: ###-#### Internet Inspection Request from: Jason Minnick all items on c/n were completed 6/25/2003 7:31:27 AM
DOC - Permit Finaled6/25/20036/25/20036/25/2003APASS
DetailsRick Jackson
Finaled by inspector at 6/25/2003 7:31:31 AM
INSP-Final Inspection5/20/20035/27/20035/27/2003AFAIL
DetailsTroy Cobbley
Provide updated map, provide immediate shutdown for the two new hvac units in the waiting area, provide sync for the strobes and temporal for the horns in the new/remodeled areas. Provide nfpa 72 forms 5/27/2003 9:05:48 AM
INSP-Final Inspection5/19/20035/20/20035/20/2003ACANC
DetailsTroy Cobbley
canceled at the fire alarm contractors request until next tuesday at 7:30 am 5/20/2003 12:07:56 PM
INSP-Final Inspection5/16/20035/19/20035/19/2003ACANC
DetailsTroy Cobbley
Phone #: ###-#### I spoke to Jason Minnick and he stated that they needed to cancel the inspection. 5/19/2003 11:03:56 AM 5/19/2003 11:04:43 AM
INSP-Conference4/29/20034/30/20034/30/2003ADONE
DetailsTroy Cobbley
todd; Phone #: ###-#### Contractor says it will be difficult to mount the manual pull station within 5' of the door as per code. I told him he will need fire dept permission to put it elsewhere. Also one induct detector will be deleted 4/30/2003 10:36:08 AM
Issue permit  4/23/2003 DONE
Inspection Record Card- Fire4/21/2003 4/21/2003 DONE
Alarm Plan Check  4/21/2003 PASS
DetailsSam Rogers
Plan modifications approved.
PLANS/APPL TAKEN TO FRONT DESK  4/21/2003 DONE
DetailsSam Rogers
Telephone call  4/21/2003 DONE
left mess that permit is ready
Issue and Print Permit  4/17/2003 DONE
Alarm Plan Check  4/16/2003 DONE
resubmittal approved.
PLANS/APPL TAKEN TO FRONT DESK  4/16/2003 DONE
Inspection Record Card- Fire4/16/2003 4/16/2003 DONE
Telephone call  4/16/2003 DONE
permit ready and fees due
INSP-Conference4/7/20034/7/20034/7/2003PDONE
DetailsTroy Cobbley
I issued a citation to Peak Electric for the installation of fire alarm devices with out approved drawings. The citation number is F000382. The citation was made out to Peak Electric and was signed for by the secretary. I can now sign a temporary occupancy per Dave Millers permission.
INSP-Final Inspection4/7/20034/7/20034/7/2003PPART
DetailsTroy Cobbley
The fie alarm was given temp with dave millers permission until it is installed and tested
Plan resubmittals received  4/4/2003  
Telephone call  4/4/2003 DONE
Telcons with Dave Miller; Dale Anderson, KJ Cor GC; Jason Minnick, AEI. Dave
is willing to give TOC but only after a citation is issued to Peak Electric who did all the installation work without a permit. The alarm permit fee will be doubled for work without a permit; advised Jason, AEI, of that, and of need to address comments in my initial review regarding smoke deteciton coverage, which were not included in the resubmittal.
Plan assigned to (SAM)11/27/2002 12/20/2002 DONE
12/20/2002 11:21:50 JWA - activity updated through activity FIRA22 from case FIR02-00473.
Alarm Plan Check  12/6/2002 FAIL
Plan deficiencies discussed with and faxed to AEI and Eidam and Assoc's.
Application received  11/27/2002  
Inspection Record Card- Fire4/21/2003