INSP-Alarm Testing | 6/24/2003 | 6/25/2003 | 6/25/2003 | A | PASS |
Rick Jackson
|
|
|
Rick,
This is the project that we spoke about yesterday. We would like to have you on-site at 7:00 am if at all possible, in order to be out of the county's way when they are ready to begin their day. If there are any problems, please call me on my cell ###-####, or at the office ###-####. Thank you.; Phone #: ###-#### Internet Inspection Request from: Jason Minnick all items on c/n were completed 6/25/2003 7:31:27 AM
|
DOC - Permit Finaled | 6/25/2003 | 6/25/2003 | 6/25/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/25/2003 7:31:31 AM
|
INSP-Final Inspection | 5/20/2003 | 5/27/2003 | 5/27/2003 | A | FAIL |
Troy Cobbley
|
|
|
Provide updated map, provide immediate shutdown for the two new hvac units in the waiting area, provide sync for the strobes and temporal for the horns in the new/remodeled areas. Provide nfpa 72 forms 5/27/2003 9:05:48 AM
|
INSP-Final Inspection | 5/19/2003 | 5/20/2003 | 5/20/2003 | A | CANC |
Troy Cobbley
|
|
|
canceled at the fire alarm contractors request until next tuesday at 7:30 am 5/20/2003 12:07:56 PM
|
INSP-Final Inspection | 5/16/2003 | 5/19/2003 | 5/19/2003 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### I spoke to Jason Minnick and he stated that they needed to cancel the inspection. 5/19/2003 11:03:56 AM 5/19/2003 11:04:43 AM
|
INSP-Conference | 4/29/2003 | 4/30/2003 | 4/30/2003 | A | DONE |
Troy Cobbley
|
|
|
todd; Phone #: ###-#### Contractor says it will be difficult to mount the manual pull station within 5' of the door as per code. I told him he will need fire dept permission to put it elsewhere. Also one induct detector will be deleted 4/30/2003 10:36:08 AM
|
Issue permit | | | 4/23/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/21/2003 | | 4/21/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/21/2003 | | PASS |
Sam Rogers
|
|
|
Plan modifications approved.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/21/2003 | | DONE |
Sam Rogers
|
|
|
|
Telephone call | | | 4/21/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 4/17/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/16/2003 | | DONE |
|
|
|
resubmittal approved.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/16/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/16/2003 | | 4/16/2003 | | DONE |
|
|
|
|
Telephone call | | | 4/16/2003 | | DONE |
|
|
|
permit ready and fees due
|
INSP-Conference | 4/7/2003 | 4/7/2003 | 4/7/2003 | P | DONE |
Troy Cobbley
|
|
|
I issued a citation to Peak Electric for the installation of fire alarm devices with out approved drawings. The citation number is F000382. The citation was made out to Peak Electric and was signed for by the secretary. I can now sign a temporary occupancy per Dave Millers permission.
|
INSP-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 | P | PART |
Troy Cobbley
|
|
|
The fie alarm was given temp with dave millers permission until it is installed and tested
|
Plan resubmittals received | | | 4/4/2003 | | |
|
|
|
|
Telephone call | | | 4/4/2003 | | DONE |
|
|
|
Telcons with Dave Miller; Dale Anderson, KJ Cor GC; Jason Minnick, AEI. Dave
is willing to give TOC but only after a citation is issued to Peak Electric who did all the installation work without a permit. The alarm permit fee will be doubled for work without a permit; advised Jason, AEI, of that, and of need to address comments in my initial review regarding smoke deteciton coverage, which were not included in the resubmittal.
|
Plan assigned to (SAM) | 11/27/2002 | | 12/20/2002 | | DONE |
|
|
|
12/20/2002 11:21:50 JWA - activity updated through activity FIRA22 from case FIR02-00473.
|
Alarm Plan Check | | | 12/6/2002 | | FAIL |
|
|
|
Plan deficiencies discussed with and faxed to AEI and Eidam and Assoc's.
|
Application received | | | 11/27/2002 | | |
|
|
|
|
Inspection Record Card- Fire | 4/21/2003 | | | | |
|
|
|
|