Permit Information
Permit NumberFIR02-00483
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 S FEDERAL WAY
Project Namealm-MICRON Bldg 24 PCS 5320
Customer Number20025320
ePlanReview 
Description
MICRON Bldg 24 PCS 5320 - TMA on CENT493 - To install fire protection safeguards on a new cabinet, containing trimethyl aluminum, on tool CENT493, in Fab Building 24, in accordance with an approved Alternate Design for TMA quantities exceeding UFC maximum allowable limits. These plans include a VESDA Laser Compact high sensitivity smoke detection panel sampling air from within the new cabinet, an explosion proof, IR/UV flame detector within the cabinet, flow monitoring of the nitrogen fire suppression agent for cabinet flooding, pressure supervision of the nitrogen supply, cabinet exhaust air flow monitoring, and a cabinet door switch interlocked to disable all chemical delivery valves. The existing building FA system will power and monitor the UV/IR smoke detector, monitor the Vesda smoke detection system for alarm and trouble, release the nitrogen suppression agent and disable chemical gas valves in event of UV/IR flame detection, supervise the nitrogen supply pressure, monitor the tool power supply and release the nitrogen in event of an emergency power off condition. The exhaust airflow switch will be monitored for alarm and trouble at the constantly attended central control room.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing12/18/200312/19/200312/19/2003PPASS
DetailsRick Jackson
cell ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
DOC - Permit Finaled12/19/200312/19/200312/19/2003PPASS
DetailsRick Jackson
Finaled by inspector at 12/19/2003 2:09:21 PM
INSP-Alarm Testing12/11/200312/12/200312/12/2003PNR
DetailsRick Jackson
cell ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino per Dan this will be rescheduled for a later date 12/12/2003 11:11:15 AM
FIR-Aging Inspection4/1/20034/1/20034/1/2003 PART
DetailsRick Jackson
talked to Dan and he is getting the engineers to get with Sam about what sequence happens when it goes into alarm or supervisory 4/1/2003 1:55:42 PM
Issue and Print Permit  12/30/2002  
Inspection Record Card- Fire12/23/2002 12/23/2002 DONE
Telephone call  12/23/2002 DONE
e mail permit ready and fees due
Plan assigned to (SAM)12/3/2002 12/20/2002 DONE
12/20/2002 16:39:28 SLR - activity updated through activity FIRA22 from case FIR02-00483.
Alarm Plan Check  12/20/2002 PASS
PLANS/APPL TAKEN TO FRONT DESK  12/20/2002 DONE
Application received  12/3/2002