INSP-Final Inspection | 3/20/2003 | 3/21/2003 | 3/21/2003 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm system finaled 3/21/2003 2:51:49 PM
|
DOC - Permit Finaled | 3/21/2003 | 3/21/2003 | 3/21/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/21/2003 2:51:53 PM
|
INSP-Final Inspection | 2/11/2003 | 2/13/2003 | 2/13/2003 | A | FAIL |
Troy Cobbley
|
|
|
repair the outside alarm bell, provide annual inspection tag for the fire sprinkler system, provide map of the fire alarm devices, provide supervision of the anti-freeze system control valve 2/13/2003 9:04:00 AM
|
Telephone call | | | 2/7/2003 | | DONE |
|
|
|
telcon from Steve Larsen, regarding decision on duct detectors in AHU's. I advised him that Mech Inspection had determined no duct detectors exist and decided none will be required at this time. Therefore they will not be required as part of the fire alarm permit inspection.
|
Meeting | | | 2/6/2003 | | DONE |
|
|
|
Per George Slane, their Mech inspector determined no work was done on these units and the AHU's were approved under the original building permit. Therefore they are not going to require duct smoke detectors on them to meet current code. Therefore there will be no duct detectors to be connected to the Fire alarm system.
|
INSP-Conference | 2/3/2003 | 2/4/2003 | 2/4/2003 | A | DONE |
Troy Cobbley
|
|
|
conference was for placement of duct smoke detectors. After speaking to Sam Rogers and George Slane I called Dixie and she said she would contact Steve Larson and try to work something out 2/4/2003 3:15:49 PM
|
Issue permit | | | 1/16/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 12/9/2002 | | 1/14/2003 | | DONE |
|
|
|
1/14/2003 15:32:09 SLR - activity updated through activity FIRA22 from case FIR02-00489.
|
Alarm Plan Check | | | 1/14/2003 | | PASS |
|
|
|
Resubmittal acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/14/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/14/2003 | | 1/14/2003 | | DONE |
|
|
|
|
Telephone call | | | 1/14/2003 | | DONE |
|
|
|
permit ready and fees due
|
Miscellaneous action | | | 1/10/2003 | | DONE |
|
|
|
Allowed Peak Alarm to take the only copy of the plan to be photocopied for our 2nd print and for them to have a copy; also took both spec booklets to revise.
|
Plan resubmittals received | | | 1/10/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/3/2003 | | HOLD |
|
|
|
Only one copy of plans submitted. Also, cannot determine if this is a modification or a new system. Discussed with Steve Larsen, who will resubmit 2 copies of plans with revisions.
|
Application received | | | 12/9/2002 | | |
|
|
|
|