Permit Information
Permit NumberFIR02-00512
StatusFinaled
Name APEX CONSULTING ENGINEERING
Site Address 285 N MILWAUKEE
Project Namealm-WESTPARK TOWNE PLAZA
Customer Number 
ePlanReview 
Description
WESTPARK TOWNE PLAZA/ FUGIAMA SUSHI REST - To extend an existing fire alarm system in the detached building at 513 Milwaukee which presently serves only two buildings, to serve the entire shopping center complex. Coverage includes sprinkler monitoring, monitoring of cooking hood fire extinguishing system, smoke detectors over alarm control panels, duct detectors for HVAC air handler shut down, manual pulls in selected sprinkler riser rooms, and an inside audible alarm located in the tenant space at 507 W. Milwaukee.
The associated building permit (BLD 02-02800) is to construct a 2,448 sq.ft. restaurant per approved plans on file. Work to include construction of interior partitions, raised floor area, two accessible restrooms, installation of a new type two hood system, and new type one hood system, construction of new one-hour rated grease duct shaft, installation of a walk-in cooler (less than 400 sq ft), installation of suspended ceiling system, installation of new exterior exit door by cutting new opening in the CMU Wall. Miscellaneous related interior finishes and kitchen appliances.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/14/20033/14/20033/14/2003PPASS
DetailsTroy Cobbley
fire alarm system finaled
DOC - Permit Finaled3/14/20033/14/20033/14/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/14/2003 3:45:59 PM
INSP-Final Inspection3/12/20033/13/20033/13/2003AFAIL
DetailsTroy Cobbley
###-#### The 12 volt power supply #2 needs 26 ah batteries, need letter from Grinnell on verification of inspectors tests orfice size, provide verification on the knox key boxes are ok with the fire dept 3/13/2003 10:02:53 AM
INSP-Alarm Testing3/12/20033/12/20033/12/2003PPART
DetailsTroy Cobbley
finished testing the duct smoke detectors and the fire sprinkler riser in Ross. Need to finish the other sprinkler risers and panel items
INSP-Final Inspection3/7/20033/7/20033/7/2003PPART
DetailsTroy Cobbley
phil; Phone #: ###-#### Tested most of the duct smoke detectors. They have been marked on the approved alarm plans. No other devices tested. Phil to provide print out of the alarm points for verification at central station 3/7/2003 4:07:04 PM
Inspection Record Card- Fire1/17/2003 1/17/2003 DONE
Issue and Print Permit  1/17/2003 DONE
Plan assigned to (SAM)12/24/2002 1/10/2003 DONE
1/10/2003 14:54:57 SLR - activity updated through activity FIRA22 from case FIR02-00512.
Alarm Plan Check  1/10/2003 PASS
PLANS/APPL TAKEN TO FRONT DESK  1/10/2003 DONE
Telephone call  1/10/2003 DONE
CALLED 1-10-03
Application received  12/24/2002