Permit Information
Permit NumberFIR02-00513
StatusFinaled
Name M2 AUTOMATION
Site Address 150 N CAPITOL BLVD
Project Namealm-CITY HALL EXP. Bsmt
Customer Number 
ePlanReview 
Description
CITY HALL EXPANSION - To replace the existing fire alarm panel and install a new fire alarm system covering all floors (3 story and bsmt) of the building addition previously occupied by ADA County, connected to the existing fire alarm panel in the front lobby of the building. System coverage includes fire sprinkler monitoring, including the fire pump, a manual alarm system, partial area smoke detection, elevator recall, duct detectors for HVAC air handler shut down, and in-duct detectors for smoke damper release, and a/v notification.
There are 5 associated building permits (BLD 02-0153-basement), (BLD 02-01413 1st floor), (BLD 02-01532 2nd floor), (BLD 02-00579 3rd floor), (BLD 02-00938 4th floor), to renovate all floors of the building addition.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final inspection  11/28/2007 PASS
Tamper switches now supervised, sprinklers installed in elevator room.
Meeting  11/27/2007 DONE
Reviewed project status with Mike Timmerman. He willl follow up with Bob Archibald to get remaining items resolved and permit finaled.
Case Summary  11/27/2007  
INSP-Alarm Testing3/17/20033/19/20033/19/2003AFAIL
DetailsRick Jackson
Rick Will 8:00 Am Work? Please call me if there is a problem with the 8:00 am time. Thanks Mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman still need tampers on pump monitored; need to test pump running and controller; otherwise all alarms tested okay 3/19/2003 4:44:07 PM
Issue permit  2/19/2003 DONE
Plan assigned to (SAM)12/24/2002 2/14/2003 DONE
2/14/2003 10:31:06 SLR - activity updated through activity FIRA22 from case FIR02-00513.
Alarm Plan Check  2/14/2003 PASS
resubmitttal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  2/14/2003 DONE
Inspection Record Card- Fire2/14/2003 2/14/2003 DONE
Telephone call  2/14/2003 DONE
permit ready
Plan resubmittals received  2/13/2003 DONE
letter received from Sam Rapp received giving details of building standby power supply.
Alarm Plan Check  1/14/2003 FAIL
Conditional approval granted to begin installation. Final inspection shall not be made until approved plans and permit is issued. Review comments discussed with and faxed to Mike at M2 Automation.
Application received  12/24/2002