Permit Information
Permit NumberFIR03-00006
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameSPR SARMC-PARKING GARAGE
Customer Number 
ePlanReview 
Description
Saint Alphonsus Regional Medical Center (East Parking Garage) - To install a Class 1, Manual, Dry Standpipe system in a new 83,600 ft/2, two-level, concrete parking garage on the east side of the Saint Alphonsus Regional Medical Center Campus. The top deck being at street level and one deck below. This garage is an open parking garage with exterior openings at the North and East sides of the structure. This building is structurally designed to support one additional future parking level. This garage is not fire sprinklered. The piped system shall comply with NFPA 14-2000, NFPA 13-1999 (where addressed), attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-02583.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/200310/31/200310/31/2003APASS
DetailsTroy Cobbley
DOC - Permit Finaled10/31/200310/31/200310/31/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 10/31/2003 8:17:55 AM
INSP-Sprinkler Rough-in/Hydro9/2/20039/2/20039/2/2003PPART
DetailsTroy Cobbley
provide as-builts to the city of boise showing the new hose vavle locations, provide EQ bracing on the 4" piping in the locations as discussed, provide signage for the stand pipe per review notes, provide verification that there is adequate clearance for hose hookup at the top north hose vavle with the fire dept. Hydro test is OK 9/2/2003 3:04:21 PM 9/2/2003 3:08:33 PM
Miscellaneous action  8/14/2003 DONE
Received a fax on a hose stations being relocated due to problems mounting them to column assemblies. Responded that it has to meet the requirements of NFPA 14:5-3.2, and denied the request.
INSP-Conference8/7/20038/11/20038/11/2003ADONE
DetailsTroy Cobbley
The sprinkler contractor is requesting the relocation of the hose valves at the south end of the project. It appears the hose vavles will still meet NFPA 14 spacing requirements but they will need to contact Bill Alexander for final approval and resubmit an as-built before final approval 8/11/2003 11:01:45 AM
INSP-Conference6/26/20036/26/20036/26/2003PDONE
DetailsTroy Cobbley
mike; Phone #: ###-#### Hose valves relocated and elevation changed. This is for the two vavles located in the egress path. OK per Bill Alexander and I. 6/26/2003 4:17:22 PM
Issue and Print Permit  3/21/2003 DONE
Plan assigned to (Bill)1/6/2003 3/20/2003 DONE
3/20/2003 14:04:45 JWA - activity updated through activity FIRA22 from case FIR03-00006.
Sprinkler Plan Check3/14/2003 3/20/2003 PART
DetailsBill Alexander
Requires earthquake resubmittals.
PLANS/APPL TAKEN TO FRONT DESK  3/20/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire3/20/2003 3/20/2003 DONE
Telephone call  3/20/2003 DONE
permit ready
Plan assigned to (Bill)3/14/2003 3/14/2003 DONE
Plan resubmittals received  3/14/2003 DONE
Sprinkler Plan Check1/6/2003 1/22/2003 FAIL
DetailsBill Alexander
1. The feed/supply main is shown as buried underneath this structures floor. Pipe shall not be run under buildings. Exception: When absolutely necessary to run pipe under buildings, special precautions shall be taken that include arching the foundation walls over the pipe, running pipe in covered trenches, and providing valves to isolate sections of pipe under buildings. (NFPA 14:4-1.2.6)
2. Provide clarification of the 2" C900 PVC piped for the sump drain line. Provide data submittal of that piping, its' drain valve, etc. Pipe or tube used in standpipe systems shall meet or exceed one of the standards in NFPA 14 Table 2-2.1 or shall be in accordance with 2-2.2 through 2-2.6. (NFPA 14:2-2.1)
3. Provide better detail on a standpipe riser/s, which includes dimensioned elevation view of the structure, the dimensioning elevation of those devices/connections, dimensioning location of required flexible connections in contrast to floor penetrations, support clamps, bracing, etc, all meeting minimum requirements of NFPA 14:6-1.
4. Provide location of the hydrants which shall be used for this facility on the "Site Plan." (NFPA 14:6-1)
5. When the installation of sprinkler heads is not involved or insignificant due to the type of work being permitted, a plan review fee equivalent to 1.05% of the total bid price shall be assessed, up to a maximum of $3,150.00 or a minimum of $105.00 (whichever is larger), and paid to the Building Official. Provide your contract price for this work in order to verify permit fee requirements meeting BCO ยง4-02-28(2-B)
Miscellaneous action  1/22/2003 DONE
Returned plans to the front desk for calling and returning denied plans - 3:15 pm.
Telephone call  1/22/2003 DONE
plans failed called for pickup
Application received  1/6/2003