Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR03-00007
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 400 S BROADWAY AVE (2ND, 3RD, 5TH FLRS)
Project NameSPR MK-PLAZA I
Customer Number 
ePlanReview 
Description
MK PLAZA I - This permit is to modify (plugging, relocating and adding) sprinklers within the TI areas on the 2nd, 3rd, and 5th floors. Modifications include replacing some (not all) existing standard spray heads with large orifice, extended coverage heads, as has apparently been done previously in other selected areas, outside the current TI areas. This permit is limited to the modifications shown on the sprinkler plans. Although the building permit includes the basement, no sprinkler work is included under this permit on the basement level.
The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
This permit is attached to building permit BLD02-02458, which is to remodel areas in the basement (about 1,000 square feet), on the 2nd floor (about 6,600 square feet), on the 3rd floor (about 5,000 square feet), and on the 5th floor (about 5,800 square feet) within an existing 111,000 square foot 6 story building. Work is to include demolition of interior nonbearing walls, repair to an existing access floor system, and repair to finishes all per approved drawings and plan review conditions on file.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro4/21/20034/22/20034/22/2003PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/21/2003 at 10:38:05 AM.
DOC - Permit Finaled4/22/20034/22/20034/22/2003PPASS
DetailsRick Jackson
Finaled by inspector at 4/22/2003 4:18:03 PM
INSP-Sprinkler Rough-in2/10/20032/11/20032/11/2003AFAIL
DetailsRick Jackson
###-#### need hanger within 12 inches from end of pipe on fifth floor; not all approved heads are installed - can verify at final; need tampers on new test header supervised; leak at jockey pump controller 2/11/2003 10:27:35 AM
Issue permit  1/22/2003 DONE
Inspection Record Card- Fire1/21/2003 1/21/2003 DONE
Telephone call  1/21/2003 DONE
Sprinkler Plan Check1/21/2003 1/21/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  1/21/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check  1/16/2003 FAIL
Conditional approval granted to begin installation without approved plans. Faxed review comments to Viking. Called Viking to discuss, but could not contact Bryan Johnson.
Application received  1/7/2003  
Case Summary    DONE