Permit Information
Permit NumberFIR03-00012
StatusFinaled
Name MOUNTAIN ALARM
Site Address 5380 W FRANKLIN RD
Project Namealm-AMERICAN RED CROSS
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm panel to provide code compliant fire sprinkler monitoring for this building. Since all system components are affected by a FAC panel replacement, a full alarm system upgrade to meet current codes is required at the time of any FAC panel replacement. Therefore the scope of this project will include a review of the entire alarm system. The existing building alarm system also includes voluntary manual pull stations at all exits at every level and audible alarm annunciation throughout the building. No visual alarms are provided.

The associated building permit (BLD 02-00410) is to perform selective demolition per plans and to remodel a 1,600 sq. ft portion of the basement to create Lab, Labeling, Mechanical & Communications rooms; remodel 820 sq. ft. on the 1st floor for a Lab area and installation of a walk-in cooler per approved plans on file. Work to include construction of interior non-bearing walls & finishes; mechanical, electrical, plumbing & fire sprinkler upgrades; suspended ceiling installation; walk-in cooler & cabinetry; and maintenance of floor/ceiling draft stop systems. NOTE: This building is fully sprinklered. A "Letter of Completion / Compliance" is required for final occupancy & use approval as a condition of this permit. PC#02-120/drs

6/18/2004 - On 5/18/2004, phone call to Lynde Jones at Mt Alarm to explain the plan modification was required to show all the security devices and the doors they are controlling beside the releasing mechanism of the fire alarm system. She stated they would get that information on the plans and resubmit. I received revised plans on 6/17/2004, started a plan review today and found that no security devices have been placed on the drawings. A resubmittal is required. I phoned Lynde to advise of the situation. She will call on Monday to set up a meeting to resolve this issue.

7/9/2004 - Received revised plans indicating the locations of the doors and the security devices associated with them. There are six (6) doors shown on the basement plan and six (6) doors shown on the first floor plan. The PDS Fire Inspector shall field verify the functionality of these doors per IFC 1003.3.1.3.4.

7/30/2004 - Received complete resubmittal. Revised plans, riser, calcs and cutsheets. Item #8 has revised battery calculations.

10/22/2004 - Revised scope of work: To replace an existing fire alarm system with an addressable FACP. The required sprinkler monitoring fire alarm system includes manual pull stations, HVAC shutdown, elevator recall/shutdown and voluntary audible/visual notification throughout.

12/14/2004 - Received a revised building layout and fire alarm system modifications. The RTS for the HVAC shutdown are now located in the ceiling tiles below the unit, the elevator machine room has been relocated on the plans to match the building. Comment #5 regarding the horn/strobe in the stairwell still applies, it is shown on the plans and should NOT be installed.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/3/20052/4/20052/4/2005APASS
DetailsTroy Cobbley
Fire alarm finally finaled! 2/4/2005 11:02:58 AM
DOC - Permit Finaled2/4/20052/4/20052/4/2005APASS
DetailsTroy Cobbley
Finaled by inspector at 2/4/2005 11:03:03 AM
INSP-Final Inspection1/26/20051/27/20051/27/2005AFAIL
DetailsTroy Cobbley
Inspection was to verify that the waterflow switch is still intermittent as far as timing. It appears that the water for the sprinkler system is surging which won't allow the flow switch to activate. I left correction notice with Mountain Alarm and Eric with Red Cross 1/27/2005 8:17:47 AM
INSP-Final Inspection1/26/20051/27/20051/27/2005ANR
DetailsRick Jackson
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Talked to Linda and the flow switch problem has been turned over to Viking 1/27/2005 8:15:50 AM
Issue permit  1/26/2005 DONE
Alarm Plan Check  1/10/2005 PASS
Plan Modification (as-built drawings). Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/10/2005 DONE
Permit Ready to Issue  1/10/2005 DONE
Inspection Record Card- Fire1/10/2005 1/10/2005 DONE
INSP-Final Inspection1/7/20051/7/20051/7/2005PFAIL
DetailsTroy Cobbley
Bells still did not ring within 90 seconds 1/7/2005 2:29:29 PM
INSP-Final Inspection1/5/20051/6/20051/6/2005PFAIL
DetailsTroy Cobbley
Waterflow did not come into panel within 90 seconds 1/6/2005 1:11:38 PM
Plan resubmittals received  1/5/2005  
INSP-Final Inspection12/16/200412/17/200412/17/2004PFAIL
DetailsTroy Cobbley
Need two a/v's relocated to within 15' of the end of the corridor on the third floor and in the basement. Replace the door holder on the first floor and provide as builts. 12/17/2004 1:49:24 PM
INSP-Alarm Testing12/14/200412/15/200412/15/2004PFAIL
DetailsTroy Cobbley
See correction notice and approved plans for items needing attention 12/15/2004 4:13:09 PM
Inspection Record Card- Fire12/14/2004 12/14/2004 DONE
CHANGE STATUS TO (ISS)  12/14/2004 DONE
has been in before
Alarm Plan Check  12/14/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/14/2004 DONE
(F) Reprint permit  12/14/2004 DONE
Plan resubmittals received  12/10/2004  
INSP-Alarm Testing12/7/200412/8/200412/8/2004AFAIL
DetailsTroy Cobbley
Inspection stopped after testing initiating devices on the first and second floors. Third floor not looked at. Elevator recall and sprinkler flow not done nor duct detectors on the roof. Monitoring company did not receive trouble for loss of phone lines, a/c power or loss of batteries. Resubmittals required. See city approved plans for specific locations and deficiencies. 12/8/2004 2:58:42 PM
Issue and Print Permit  11/4/2004 DONE
Alarm Plan Check  11/3/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/3/2004 DONE
Miscellaneous action  11/3/2004 DONE
Faxed comments to Eric Beasley (Red Cross)
Permit Ready to Issue  11/3/2004 DONE
Inspection Record Card- Fire11/3/2004 11/3/2004 DONE
Plan resubmittals received  10/28/2004 DONE
Alarm Plan Check  10/22/2004 FAIL
Resubmittal required. Faxed comments to Lynde Jones, Mt Alarm
Telephone call  10/22/2004 DONE
I called Lynde to go over the comments. I requested she come down and we will review comments and compare plans.
Telephone call  10/22/2004 DONE
I called Derald Watts, owner's rep. to advise him of the status of this permit and express our concern at the time it is taking to get the alarm system up to code. He was appreciative and unaware of the history. Reviewed activity log with him. He indicated contracts associated with the original bldg permit were handled by corporate. He will follow up with them on how to proceed on finding a way to expedite this work to satisfactory completion.
Plan resubmittals received  10/15/2004  
INSP-Alarm Testing8/3/20048/4/20048/4/2004PFAIL
DetailsTroy Cobbley
Provide resubmittals showing the correct wiring for initiating zones and show door hold opens. Provide "Request to Exit" buttons per IFC 1003.3.1.3.4. See review notes. Provide correct count of horns. Provide verification of note #9. Need to retest pull stations and fire sprinkler items and horns on second floor. A re-inspection fee will apply upon the next inspection. 8/4/2004 4:25:07 PM
Issue and Print Permit  8/2/2004 DONE
Inspection Record Card- Fire7/30/2004 7/30/2004 DONE
Telephone call  7/30/2004 DONE
Spoke with caholly and told her that permit is ready & fees///7/30/04 2:30pm BAM
Alarm Plan Check  7/30/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/30/2004 DONE
Permit Ready to Issue  7/30/2004 DONE
Plan resubmittals received  7/29/2004  
Alarm Plan Check  7/9/2004 FAIL
Resubmittal required. Brent stated there are door hold-opens within the building, they are not included on the plans or riser.
Telephone call  7/9/2004 DONE
Called Rob Bailey (Mt Alarm), (Brent and Lynde were out today) to request cut sheets for the magnetic lock relay and a revised battery calculation.
Plan resubmittals received  7/2/2004  
Alarm Plan Check  6/18/2004 FAIL
Resubmittal required. Phone call to Lynde Jones at Mt Alarm. The security devices were not shown on the plans that were resubmitted, the responsible party has left for the day and will have him call to make an appointment on Monday.
Plan resubmittals received  6/17/2004  
Telephone call  6/15/2004 DONE
Spoke with Lynde Jones at Mt Alarm. She will track down the drawings and ensure they are resubmitted no later than tomorrow.
Telephone call  5/27/2004 DONE
HOLD. Brent from Mt Alarm, the floor plans that have been submitted do not show the correct doors and locations. They will resubmit plans with the proper door layout.
Telephone call  5/18/2004 DONE
I spoke with Linde Jones, she was unsure of the exact nature of the resubmittal, except she was told to add relays to the FACP to deactivate the security doors. I explained that we require the security hardware shown on the affected doors on the plans so our inspector know which and how many doors to test. I stated that I would accept these plans if someone marked them up to reflect the security hardware and locations. She will have Brent call me and we will determine the additional information required to pass the Plan Modification to the original permit.
Plan resubmittals received  5/4/2004 DONE
INSP-Final Inspection3/19/20043/19/20043/19/2004PFAIL
DetailsTroy Cobbley
Plans need to be resubmitted showing the new door magnet/security interface. Items tested today are both phone lines, vavle tamper switch and battery calculations which are ok. The smoke detector is now approved to be used with this panel. 3/19/2004 4:34:10 PM
INSP-Final Inspection6/4/20036/6/20036/6/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 6/4/2003 at 9:39:28 AM. Contact: ###-####. started to test sprinkler flow but couldn't locate inspectors test (after checking the exterior it appears to be on the northwest side of the building); need compatibility for smoke above panel; this is all that was done for today; they will reschedule for 6/9/03 to finish 6/6/2003 5:07:43 PM
INSP-Final Inspection3/18/20033/19/20033/19/2003PFAIL
DetailsTroy Cobbley
provide the correct smoke detector as per the submittals, verify a dedicated circuit, provide map, verify battery standby once the dedicated circuit is found, provide sign on door, test all initiating devices and verify signals 3/19/2003 4:14:10 PM
INSP-Final Inspection2/19/20032/21/20032/21/2003PCANC
DetailsTroy Cobbley
nicole ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--cancel per pam
Inspection Record Card- Fire1/27/2003 1/27/2003 DONE
Telephone call  1/27/2003 DONE
permit ready and fees due
Issue permit  1/27/2003 DONE
Alarm Plan Check  1/24/2003 PASS
PLANS/APPL TAKEN TO FRONT DESK  1/24/2003 DONE
Plan assigned to (SAM)1/10/2003 1/24/2003 DONE
1/24/2003 17:58:17 SLR - activity updated through activity FIRA22 from case FIR03-00012.
Plan resubmittals received  1/16/2003 DONE
Application received  1/10/2003  
Alarm Plan Check  1/14/2002 FAIL
faxed Mountain alarm the application with missing items circled for resubmittal
Inspection Record Card- Fire7/30/2004    
Inspection Record Card- Fire12/14/2004