INSP-Final Inspection | 3/20/2003 | 3/21/2003 | 3/21/2003 | A | PASS |
Troy Cobbley
|
|
|
robert; Phone #: ###-#### Fire alarm system finaled 3/21/2003 8:57:10 AM
|
DOC - Permit Finaled | 3/21/2003 | 3/21/2003 | 3/21/2003 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/21/2003 8:57:35 AM
|
INSP-Alarm Testing | 3/19/2003 | 3/20/2003 | 3/20/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/19/2003 at 11:30:48 AM. Contact: ###-####. duct detectors powered by panel; need calc's and it appears larger amp batteries will be needed; need to test sprinkler controls/flow 3/20/2003 10:37:28 AM
|
Miscellaneous action | | | 3/19/2003 | | PASS |
|
|
|
Received resubmittal as required in review comment #1 of 1/24/03, for a battery box required to house batteries which are larger than FAC panel can hold. Approved subject to satisfactory field inpection of installation.
|
Alarm Plan Check | | | 3/18/2003 | | PASS |
|
|
|
Plans modification approved with conditions to be field verified
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/18/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/18/2003 | | 3/18/2003 | | DONE |
|
|
|
|
Issue permit | | | 3/18/2003 | | |
|
|
|
|
Plan resubmittals received | | | 3/10/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/5/2003 | | DONE |
|
|
|
telcon from Bob Coulter. He now reports that there are HVAC duct detectors which require monitoring. I indicated a resubmittal would be required to add to the FA system.
|
Issue permit | | | 1/27/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/24/2003 | | PASS |
|
|
|
approved with CONDITIONS
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/24/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/24/2003 | | 1/24/2003 | | DONE |
|
|
|
|
Telephone call | | | 1/24/2003 | | DONE |
|
|
|
permit ready
|
Plan assigned to (SAM) | 1/10/2003 | | 1/23/2003 | | DONE |
|
|
|
1/23/2003 11:49:41 JWA - activity updated through activity FIRA22 from case FIR03-00009.
|
Plan resubmittals received | | | 1/16/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/14/2003 | | FAIL |
|
|
|
copy of application faxed back to Mtn Alarm with missing items circled.
|
Application received | | | 1/10/2003 | | |
|
|
|
|