INSP-Final Inspection | 11/4/2010 | 11/4/2010 | 11/4/2010 | A | PASS |
Forrest France
|
|
|
Permit finaled.
|
FIR-Aging Inspection | 11/3/2010 | 11/3/2010 | 11/3/2010 | | PASS |
Forrest France
|
|
|
|
FIR-Aging Inspection | 8/2/2010 | 8/2/2010 | 8/10/2010 | | PASS |
Forrest France
|
|
|
Okay for final
|
FIR-Aging Inspection | 5/21/2010 | 5/21/2010 | 5/21/2010 | | PASS |
Forrest France
|
|
|
|
Case Summary | | | 4/13/2005 | | |
|
|
|
|
Telephone call | | | 8/13/2003 | | DONE |
|
|
|
left mess that plans are ready to pickup & no fee
|
Issue and Print Permit | | | 7/31/2003 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/31/2003 | | DONE |
|
|
|
|
Telephone call | | | 7/30/2003 | | |
|
|
|
The applicant on the latest resubmittal for the Boise airport was Dante Frassa. I called and spoke with him regarding the quantity of plans I had as we are only storing two sets for resubmittals. I gave him a choice to deliver another set, or accept one set back. He stated that one set back would be sufficient. Therefore only one set was returned.
|
Alarm Plan Check | | | 7/30/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/30/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/30/2003 | | 7/30/2003 | | DONE |
|
|
|
|
Telephone call | | | 7/30/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan resubmittals received | | | 7/24/2003 | | |
|
|
|
|
Plan resubmittals received | | | 7/24/2003 | | |
|
|
|
|
Alarm Plan Check | | | 6/24/2003 | | FAIL |
|
|
|
Plan Modification. Resubmittal required. Comments faxed to Peter Petroni 6/24/2003.
|
Plan resubmittals received | | | 6/18/2003 | | DONE |
|
|
|
|
INSP-Alarm Testing | 5/12/2003 | 5/14/2003 | 5/14/2003 | A | FAIL |
Rick Jackson
|
|
|
tested all AHU's for shutdown and smoke/fire damper shutdown - dampers closed on AHU shutdown; tested all overhead doors except for baggage system doors - all okay; still need to test dry sprinkler system and baggage system doors; will need to reverify the alarm system at final 5/14/2003 12:45:12 PM
|
INSP-Alarm Testing | 5/9/2003 | 5/12/2003 | 5/12/2003 | P | FAIL |
Rick Jackson
|
|
|
audible alarms in mechanical rooms; smoke/fire dampers aren't when AHU's are in fault; tested notification in all areas - okay; 5/12/2003 4:35:54 PM
|
INSP-Final Inspection | 5/8/2003 | 5/9/2003 | 5/9/2003 | A | FAIL |
Rick Jackson
|
|
|
###-#### robert Node 4 has ground fault; labels on several detectors not correct - see mapnet listing; strobes overspaced in mezzanine; nned to test dry sprinkler system and all troubles for TAC panels; need to test alarm condition for proper noise levels through speakers; need to drop test all overhead doors; ned to test troubles on main FACP; need programmed button labels on main FACP 5/9/2003 5:00:02 PM
|
Override - Parcel Holds | | | 5/8/2003 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2003 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 5/1/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 5/1/2003 | | 5/1/2003 | | DONE |
|
|
|
|
Telephone call | | | 5/1/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Override - Parcel Holds | | | 5/1/2003 | | |
|
|
|
|
Issue permit | | | 5/1/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/30/2003 | | PASS |
|
|
|
Per telcon with Peter Petroni, Simplex, questions resolved to complete the review.
|
Plan resubmittals received | | | 4/25/2003 | | HOLD |
|
|
|
Resubmittal received 4/7. Cannot complete evaluation without further explanation of plan submittal. Hold review or call-back from Simplex.
|
Issue permit | | | 3/19/2003 | | |
|
|
|
|
Alarm Plan Check | | | 3/13/2003 | | PASS |
|
|
|
Resubmittal plans acceptable
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/13/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/13/2003 | | 3/13/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/13/2003 | | DONE |
|
|
|
CALLED LEFT MESSAGE 3-13-03
|
Plan resubmittals received | | | 2/19/2003 | | DONE |
|
|
|
|
Meeting | | | 2/13/2003 | | DONE |
|
|
|
Meeting with Rod Ludlow, CSHQA and Stepahnie Cribbs, Simplex to review plans. Identified items needing revision on plans. List of revisions faxed to Simplex. Stephanie to revise plans accordingly and resubmit 3 complete sets of revised drawings.
|
Alarm Plan Check | | | 2/7/2003 | | FAIL |
|
|
|
Plan modifications not adequately described; matrix inadequate to verify proper operation of PA systems. Called Simplex, Stepahnie to discuss with Peter Petroni and CSHQA and decide who could come in to discuss the plans. Hold further plan review until resolved; no written comments sent out.
|
Plan assigned to (SAM) | 1/21/2003 | | 1/29/2003 | | DONE |
|
|
|
1/29/2003 09:38:09 JWA - activity updated through activity FIRA22 from case FIR02-00005.
|
Application received | | | 1/21/2003 | | |
|
|
|
|